Viessmann Vitobloc 200 EM-50/81 Operating Instructions Manual page 53

Block-type thermal power plant module for natural gas operation
Table of Contents

Advertisement

Trouble-shooting
error message
fault clearance
tightness test fails
alternator overvolt-
age
emergency shut-
down
maintenance interval
exceeded
exhaust gas counter
pressure
faulty heating water
pump
fault caused by
knocking
maximum gas pres-
sure
faulty ignition
maximum oil level
faulty oil pressure
1)
an error message is deemed to have been repeated, when the same fault is indicated again with a new time, after function key F8 has been
pressed (i.e. after the time at which the key has been pressed).
Table 10 Plain text fault messages displayed on the module control of an CHP module Vitobloc 200 that cannot be acknowledged
by pressing function key F8
VITOBLOC 200 Operating instructions for the natural gas-fuelled CHP module
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
possible cause of the fault
optional test device for the gas tightness
1)
gas valve(s) not right
alternator control defective
1)
emergency shut-down message
1)
(-X1/22-23): internal or external overtemper-
ature protection switch, external gas warning
device, fire alarm etc.
maintenance interval exceeded, plant blocks
1)
itself automatically
optional exhaust gas counter pressure moni-
1)
toring has tripped
external pump monitoring
1)
(-X1/28-29)
optional knocking monitoring has tripped
1)
optional maximum gas pressure monitoring
1)
gas pressure too high
ignition trigger has switched off
1)
short circuit in the ignition system
irregular ignition pick-up signals
optional maximum oil level monitoring has
1)
tripped
machine over-filled
automatic oil refill mechanism defective
oil pressure while machine does not run
1)
oil pressure transducer defective
53