Commissioning

3
Commissioning
3.1

Authorized personnel

NOTE
The commissioning which is to be car-
ried out by the factory service centre
must be applied for with the relevant
notification well in time, i.e. at least 4
weeks before the desired date.
CAUTION
Only a specialist firm with personnel
suitably trained for this assignment by
the CHP module manufacturer is au-
thorized to carry out the initial start-up
of the CHP module. The accident pre-
vention regulations must be observed.
LIABILITY.
The initial start-up of the CHP module
shall be carried out in consultation with
the plant manufacturer and the plant
operator and in the presence of their
authorized representatives.
24
Only suitably qualified personnel are authorized to
check the installation and to carry out the commis-
sioning.
Never let the engine start dry. i.e. without being
filled with lubrication oil or coolant.
When starting the engine, do not use any addition-
al starting aid (such as a start pilot).
Do not switch off the engine, when running under
full load, let it idle for approx. 5 min, so as to facili-
tate the temperature compensation especially at
the exhaust gas turbocharger.
Never fill cold coolant into an overheated engine.
Do not fill in engine oil above the maximum notch
at the dipstick. This can severely damage the en-
gine.
Make sure that the control and monitoring equip-
ment (alternator charging light, oil pressure, cool-
ant temperature) function properly.
The gaseous fuel has to meet the minimum re-
quirements as per Table 3. Only use fuels that
meet specifications, otherwise the manufacturer's
liability for defects is forfeited.
Before start-up, check the fuses in the control cab-
inet and replace them where necessary
Operating instructions for the natural gas-fuelled CHP module VITOBLOC 200
DANGER
Incorrect or improperly installed fuses
can lead to an increased risk of fire! For
that reason always position fuses cor-
rectly and insert without applying force.
Only use identically constructed types
with the indicated triggering characteris-
tics.