Fault Messages From The Chp Module That Cannot Be Acknowledged - Viessmann Vitobloc 200 EM-50/81 Operating Instructions Manual

Block-type thermal power plant module for natural gas operation
Table of Contents

Advertisement

Trouble-shooting
7.1

Fault messages from the CHP module that cannot be acknowledged

error message
fault clearance
emergency stop
minimum oil level
minimum cooling
water pressure
minimum gas pres-
sure
safety temperature
alternator tempera-
ture
sound hood tem-
perature
faulty fan
faulty cooling water
pump
minimum oil pres-
sure
50
release emergency stop button at the
door of the module control panel with
key or release type-specific external
emergency stop as instructed
acknowledge fault with function key F8;
call customer service if error message
is repeated
check lubrication oil reserves at the
inspection glass on the left front side of
the module:
-
if oil is missing, have the lubrication
oil tank re-filled;
-
in the event of an oil leakage at the
module call customer service im-
mediately.
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
establish, whether the gas supply is
interrupted
acknowledge fault with function key F8;
call customer service if error message
is repeated
call customer service
let the alternator cool down (1/2 hour)
acknowledge fault with function key F8;
call customer service if error message
is repeated
let the module cool down (1/2 hour)
acknowledge fault with function key F8;
call customer service if error message
is repeated
call customer service
call customer service
acknowledge fault with function key F8;
call customer service if error message
is repeated
Operating instructions for the natural gas-fuelled CHP module VITOBLOC 200
possible cause of the fault
emergency stop button has been pressed
external emergency stop button (-X1/10-11)
has been pressed
safety temperature limiter has tripped
control CPU: self-monitoring has switched off
1)
(CPU inactive)
floating switch of the automatic oil refill
mechanism has switched off
oil tank empty or refill cock closed
1)
cooling water pressure switch has tripped,
1)
pressure too low
gas pressure switch has tripped, gas pres-
sure too low, filter dirty
1)
STB has tripped
alternator overheated
1)
sound hood thermostat has tripped
1)
thermostat relay in the fan or in the fuse has
tripped
motor protecting switch for the pump has
switched off
engine oil pressure too low
1)
oil pressure transducer defective