Viessmann Vitobloc 200 EM-50/81 Operating Instructions Manual page 41

Block-type thermal power plant module for natural gas operation
Table of Contents

Advertisement

Programming
No
.
Parameter
15
maximum exhaust gas
temperature A
16
minimum exhaust gas
temperature A
17
exhaust gas temperature
release
18
battery
undervoltage
19
starter limit
firing speed
20
set speed
overspeed
21
fan
start-up time/after-run
time
22
cooling water pump
start-up time/after-run
time
23
temperature controller
minimum
24
temperature controller
KP/TN
25
governor
1 = 10 – 0
V
2 = 0 – 5
V
26
after-run time of the en-
gine
27
alternator overcurrent
VITOBLOC 200 Operating instructions for the natural gas-fuelled CHP module
Left value/Function
time delay (e.g. 0 sec)
waiting time (e.g. 120 sec)
waiting time (e.g. 5 sec)
time delay (e.g. 20 sec)
limit, at which the starter will be
switched off (e.g. 450 rpm)
set value for the speed
start-up time until module start
start-up time until module start
control valve minimum opening
angle (e.g. 10 % = 1
V
)
active from start-up time until the
end of the pump's after-run time
KP value (e.g. 5.0)
amplification factor of the regula-
tors
-----------------------------------------
after-run time of the engine under
no load after the alternator con-
tactor has been switched off
time delay (e.g. 1 sec)
Right value/Function
maximum limit (e.g. 700 °C)
if the limit set at this temperature sensor is
exceeded by the set time delay, the machine
will trip
minimum limit (e.g. 75 °C)
the temperature sensor must have exceeded
this limit after the start of the machine and
after the set waiting time, otherwise the ma-
chine will trip
(sensor function monitoring)
release temperature limit (e.g. 300 °C)
if the maximum exhaust gas temperature limit
has been exceeded, the temperature value
must drop below 300 °C for at least 5 sec,
before the fault can be acknowledged
minimum limit
if the battery/24
V
control voltage drops
below this limit, the machine will trip after the
time delay
limit, at which the control recognizes the
started engine and does not repeat the start
(e.g. 650 rpm)
maximum limit of the overspeed
if the set limit is exceeded, the machine will
trip
after-run time (e.g. 30 min)
active from the „warm-up limit" (60 °C) and
module start
10 sec after-run at <60 °C
after-run time (e.g. 30 min)
active from the „warm-up limit" (60 °C) and
module start
10 sec after-run at <60 °C
reserve
TN value (e.g. 2.0)
re-setting time of the regulator
type 1 10 – 0 V (GAC)
starts regulating at 8 V = 1 500 rpm
10 V = approx. 1 450 rpm
0 V = approx. 1 800 rpm
type 2 0 – 5 V (Heinzmann)
starts regulating at 1 V = 1 500 rpm
0 V = approx. 1 450 rpm
5 V = approx. 1 800 rpm
maximum limit
if the set limit set is exceeded by the set time
delay, the machine will trip
41