Viessmann Vitobloc 200 EM-50/81 Operating Instructions Manual page 52

Block-type thermal power plant module for natural gas operation
Table of Contents

Advertisement

Trouble-shooting
error message
fault clearance
feeder circuit-breaker
system-tie circuit
breaker
faulty Lambda regu-
lator
system trouble
(message only.)
battery undervoltage
external fault
Lambda start posi-
tion
engine does not stop
faulty sensors
system protection
defective
faulty connection
minimum exhaust
gas temperature
52
switch on the feeder circuit-breaker
acknowledge fault with function key F8;
call customer service if error message
is repeated
check/switch on on-site coupling switch
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
the module continues to work in the
automatic mode while being connected
with the mains, when an external re-
quest is made
acknowledge fault with function key F8;
call customer service if error message
is repeated
check the battery voltage
acknowledge fault with function key F8;
call customer service if error message
is repeated
eliminate the fault on site and
acknowledge with function key F8
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
Operating instructions for the natural gas-fuelled CHP module VITOBLOC 200
possible cause of the fault
feeder circuit-breaker has failed due to the
thermal monitoring or has tripped as a result
of „Faulty alternator contactor"
1)
feedback from the on-site coupling switch
incorrect
1)
Lambda control does not reach the set value
1)
engine mixture too fat, too lean, false air
probe defective
faults and breakdowns in the local grid
1)
battery or charger defective
1)
external fault on site
(contact –X1/26-27)
Lambda control valve does not reach the
1)
start position
control valve defective
inadmissible speed while the machine does
1)
not work
starter defective
alternator contactor defective
data connection with the analog box defec-
1)
tive
analog box defective
cable breakage
data connection with the line protection de-
1)
fective
line protection cart defective
during isolated operations only
1)
engine erratic or instable
nd
2
isolated modulo
exhaust gas does not reach the required
1)
minimum temperature after the engine has
been started
sensor short-circuited