Viessmann Vitobloc 200 EM-50/81 Operating Instructions Manual page 51

Block-type thermal power plant module for natural gas operation
Table of Contents

Advertisement

Trouble-shooting
error message
fault clearance
cooling water tem-
perature
maximum exhaust
gas temperature
starting speed
< 50 rpm
firing speed
rpm
speed range
overspeed
underspeed/
pick-up
synchronization
faulty
alternator undervolt-
age
alternator overcur-
rent
alternator load im-
balance
reverse power
faulty output regula-
tor
faulty alternator
contactor
VITOBLOC 200 Operating instructions for the natural gas-fuelled CHP module
let the engine cool down
acknowledge fault with function key F8;
call customer service if error message
is repeated
let the exhaust gas temperature cool
down below 300 °C (display: see Fig. 3)
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
acknowledge fault with function key F8;
call customer service if error message
is repeated
possible cause of the fault
temperature of the engine cooling water too
high, no heat reduction on site
1)
exhaust gas temperature exceeds the limit
spark plug defective, ignition coil defective
ignition cables defective, ignition trigger
1)
defective
engine setting too fat
sensor defective
starter does not engage
1)
battery empty, starter defective
pick-up defective, cable breakage
engine does not start
1)
throttle does not open
air filter dirty
engine run erratically
1)
speed control system defective, worn out or
incorrectly set
speed control system defective, worn out or
1)
incorrectly set
engine stalled or pick-up defective
1)
engine speed erratic
1)
mains frequency erratic
engine speed too low
1)
alternator control defective
alternator overloaded or alternator control
1)
defective
different phase loads or contact problems on
1)
site
gas, ignition or speed control problems,
1)
alternator driven by the mains
output deviation, control system defective
1)
dirty exhaust gas heat exchanger and/or air
filter
alternator contactor does not open correctly
1)
or feedback defective
51