5
Operation
5.3
Control via I/O interface
5.3.1
General
If the controller is activated via the I/O interface [X2], only the record selection operating mode is avail
able. The operating modes of direct mode and jogging are not possible.
Record 0 is reserved for homing. The records 1 ... 31 configured with the FCT are selected as desired by
the higher-order controller via the binary coded inputs DIN1 ... DIN5.
The other inputs and outputs serve to start the selected record or to output status messages, for ex
ample.
5.3.2
Communication
Communication takes place via the I/O interface [X2].
Note
Make sure to use PNP I/Os
Pin
Function
1
Output:
Ready for enable
2
Input 1 (value 1)
3
Input 2 (value 2)
4
Input 3 (value 4)
5
Input 4 (value 8)
6
Input 5 (value 16)
7
Output +24 V
8
Input: start record
9
Input:
enable drive
10
Input: acknowledge error
11
Output:
drive enabled
12
Output: error
13
Output: acknowledge start
14
Output: motion complete
15
0 V
Tab. 5.9 Description of the input and output interface [X2]
Festo – EXCM-30/-40-...-PF-EN – 1603 – English
Description
RDYEN
= 0
Not ready for enable
= 1
Ready for enable
DIN1
Record selection, records 0 ... 31
(Record 0 = homing)
DIN2
DIN3
The inputs are evaluated together.
DIN4
DIN5
24 V logic
Logic voltage +24 V
START
Start record or homing run though rising edge
ENABLE
= 0
Block drive and operation
= 1
Enable drive and operation
RESET
Acknowledge error through rising edge
ENABLED
= 0
Drive and operation blocked
= 1
Drive and operation enabled
FAULT
= 0
No error
= 1
Error is present
ACK
= 0
Ready for start
= 1
Start carried out
MC
= 0
Positioning task active
= 1
Positioning task completed
(possibly with error)
GND24
Logic voltage reference potential
45