Electrical Installation; Fig. 1 Ax8911: Connection To X15 And X25 - Beckhoff AX8-1 Series Documentation

Twinsafe drive option
Table of Contents

Advertisement

Operation
5.2.3.1
Control cabinet / terminal box
The TwinSAFE components must be installed for operation in a control cabinet or terminal box with at least
IP54 protection according to IEC 60529.
5.2.4

Electrical installation

5.2.4.1
Digital inputs X15, X25
With the AX8911 TwinSAFE drive option installed, the inputs X15 (axis "A") and X25 (axis "B") are used for
the STO inputs of the axis or axes.
Contacts 1 and 2 of the connection X15 are the STO inputs for axis "A". Axis "A" can be moved if both
signals are logic 1 (24 V
torque-free.
Contacts 1 and 2 of the connection X25 are the STO inputs for axis "B". Axis "B" can be moved if both
signals are logic 1 (24 V
torque-free.
Fig. 1: AX8911: Connection to X15 and X25
A plug connector is required in each case to connect signals to X15 and, in the case of two-channel axis
modules, to X25 also.
View
Wire type
Wire cross-section (solid wire)
Wire cross-section (fine wire)
Wire cross-section – fine wire (with ferrule without plastic collar)
Wire cross-section – fine wire (with ferrule with plastic collar)
18
). STO is triggered for axis "A" if one of the signals is logic 0. Axis "A" is switched
DC
). STO is triggered for axis "B" if one of the signals is logic 0. Axis "B" is switched
DC
Terminal
Connection
point
1
STO input 1
2
STO input 2
3
Digital input 3
(Filter time 8 µs)
4
Digital input 4
(Filter time 8 µs)
Version: 1.0.0
Strip length
Clamping method
9 mm
push in
Wire cross-section
0.14 mm² - 1.5 mm²
0.14 mm² - 1.5 mm²
0,25 mm² - 1.5 mm²
0,25 mm² - 1 mm²
AX8911 - TwinSAFE Drive Option