Honeywell SmartVFD HVAC2 Applications Manual page 78

Table of Contents

Advertisement

Code
Parameter
P18.3
Fire mode
frequency preset
P18.4
Fire mode
activation close
P18.5
Fire mode
activation open
Table 25. Quick setup parameters. (Continued)
Min
Max
Unit Default
P3.1
P3.2
Hz
0
Varies
0
Varies
78
ID
8.00
1598 Fire mode frequency preset
NOTE!
locked when fire mode is active. To
change the parameter you have to
disable fire mode.
6
1619 Digital input normal close
As parameter 5.1
NOTE!
locked when fire mode is active. To
change the parameter you have to
disable fire mode.
0
1596 Digital input normal open
As parameter 5.1
NOTE!
locked when fire mode is active. To
change the parameter you have to
disable fire mode.
Note
This parameter will be
This parameter will be
This parameter will be
31-00108—07