Sleep setpoint boost
Setpoint boost time
Sleep max loss
Sleep loss check time
These parameters manage a more complex sleep
sequence. After the time in P14.12, the setpoint is
increased of the term in P14.14, for the time in
P14.15. This will cause a higher output frequency.
Frequency reference is then forced at minimum
frequency and the feedback value is sampled.
If the variation on the feedback value stays then
lower than P14.16 for the time in P14.17, the
drive will enter sleep condition.
If this sequence is not needed, then program
P14.14 = 0%, P14.15 = 0 s, P14.16 = 50%, P14.17
= 1 s.
Process unit source selection
Monitor V4.5 can show a process value,
proportional to a variable measured by the drive.
Source variables are:
0
= PID feedback value (max: 100%)
1
= Output frequency (max: fmax)
2
= Motor speed (max: nmax)
3
= Motor torque (max: Tnom)
4
= Motor power (max: Pnom)
5
= Motor current (max: Inom)
Process unit decimal digits
Number of decimals shown on monitor V4.5.
Process unit min value
Value shown on V4.5 when source variable is at its
minimum.Proportionality is kept if source
overtakes the minimum.