Code
Parameter
P14.10
Error inversion
P14.11
Sleep minimum
frequency
P14.12
Sleep delay
P14.13
Wake up error
i
P14.14
Sleep setpoint
boost
P14.15
Setpoint boost
time
P14.16
Sleep maximum
loss
P14.17
Sleep loss check
i
time
P14.18
Process unit
i
source select
Table 39. PID control parameters. (Continued)
Min
Max
0
1
0,00
P3.2
0
3600
0,0
100,0
0,0
50,0
0
60
0,0
50,0
1
300
0
5
111
Unit Default
ID
0
340
Hz
25,00
1016 Threshold for enter sleep
s
30
1017 Delay for enter sleep
%
90
1018 Threshold for exit sleep
%
10,0
1071 Referred to setpoint
s
10
1072 Boost time after P14.12
%
5,0
1509 Referred to feedback value after
s
30
1510 After boost time P14.15
0
1513
Note
0 = Direct
1 = Inverted
boost
0
= PID feedback value
1
= Output frequency
2
= Motor speed
3
= Motor torque
4
= Motor power
5
= Motor current