Run the no-load tests without the motor
being connected to the process, if possible. If
this is impossible, secure the safety of each
test prior to running it. Inform your co-
workers of the tests.
Switch off the supply voltage and wait up until
the drive has stopped.
Connect the motor cable to the motor and to
the motor cable terminals of the frequency
converter.
See to that all Start / Stop switches are in Stop
positions.
Switch the mains ON.
Repeat test 7A or 7B.
9
Perform an identification run (see "Motor
identification" on page 128), especially if the
application requires a high startup torque or a
high torque with low speed.
10 Connect the motor to the process (if the no-
load test was running without the motor being
connected).
Before running the tests, make sure that this
can be done safely.
Inform your co-workers of the tests.
Repeat test 7A or 7B.
Startup Wizard
Honeywell HVAC2 runs the startup wizard at
initial power-up and whenever the drive is reset to
factory defaults.
The Start-up wizard content is shown below. It
always asks the basic parameters (P1.1-P16.1). If
you Activate the fire mode parameters with P16.1,
it will go through rest of the Fire mode
parameters.
Start-Up Wizard Parameter Group
P1.1 Motor Nominal Voltage
P1.2 Motor Nominal Frequency
P1.3 Motor Nominal Speed
P1.4 Motor Nominal Current
P1.5 Motor Cos phi (Power Factor)
P1.7 Current Limit
P1.23 Energy Optimization
P3.1 Min. Frequency