STALL TIME
This time can be set between 0.00 and 300.00s.
This is the maximum time allowed for a stall
stage. The stall time is counted by an internal
up/down counter.
If the stall time counter value goes above this
limit the protection will cause a trip (see
P12.5).See Figure "Stall time calculation" on
page 165.
Par.12.12
Stall
No stall
Fig. 63. Stall time calculation
165
Stall time counter
Trip area
Trip/warning
Par. 12.5
Time
31-00108—07