Honeywell SmartVFD HVAC2 Applications Manual page 110

Table of Contents

Advertisement

Code
Parameter
P14.4
Feedback source
selection
P14.5
Feedback value
minumum
P14.6
Feedback value
i
maximum
P14.7
P gain
i
P14.8
I time
i
P14.9
D time
i
Table 39. PID control parameters. (Continued)
Min
Max
0
Varies
0,0
50,0
10,0
300,0
0,0
1000,0
0,00
320,00
0,00
10,00
110
Unit Default
ID
1
334
%
0,0
336
%
100,0
337
%
100,0
118
s
10,00
119
s
0,00
132
Note
0
= AI1
1
= AI2
2
= ProcessDataIn1
(0 -100%)
3
= ProcessDataIn2
(0 -100%)
4
= ProcessDataIn3
(0 -100%)
5
= ProcessDataIn4
(0 -100%)
6
= AI2-AI1
7
= AIE1
8
= Temperature input 1
9
= Temperature input 2
10
= Temperature input 3
Value at minimum signal
Value at maximum signal
Proportional gain
Integrative time
Derivative time
31-00108—07

Advertisement

Table of Contents
loading

Table of Contents