Table 59. Status word (output process data)
Bit
Value = 0
B4, W
No alarm
B5, AREF Ramping
B6, Z
-
B7 - B15
-
General status word (output process data)
Information about the status of the device and
messages is indicated in the General status word.
The General status word is composed of 16 bits
the meanings of which are described in the table
below:
Description
Value = 1
Alarm active
Speed reference
reached
Drive is running at zero
speed
-
Table 60. General status word (output process
Bit
Value = 0
B0, RDY
Drive not
ready
B1, RUN Stop
B2, DIR
Clockwise
B3, FLT
No fault
B4, W
No alarm
B5, AREF Ramping
B6, Z
-
B7, F
-
B8 - B12 -
Bit
I/O
B13
1
B14
0
B15
0
179
data)
Description
Value = 1
Drive ready
Run
Counter-clockwise
Fault active
Alarm active
Speed reference reached
Drive is running at zero
speed
Fieldbus control active
-
Control place
PC
tool
Keypad
0
0
1
1
1
0
Fieldbus
0
0
1