Set the parameters of group 1 according to
the requirements of your application. At least
the following parameters should be set:
motor nominal speed ("Quick setup
parameters (Virtual menu, shows when par.
16.2 = 1)" on page 73)
motor nominal current ("Quick setup
parameters (Virtual menu, shows when par.
16.2 = 1)" on page 73)
application type ("Active fire mode parameter
group" on page 172)
You will find the values needed for the
parameters on the motor rating plate.
7
Perform test run
Test A or Test B:
A)
Control from the I / O terminals:
Turn the Start/Stop switch to ON position.
Change the frequency reference
(potentiometer).
Check the Monitoring Menu and make sure
that the value of Output frequency changes
according to the change of frequency
reference.
Turn the Start / Stop switch to OFF position.
B)
Control from the keypad:
Select the keypad as the control place with
par 2.1. You can also move to keypad control
by pressing Loc / Rem button or select Local
control with par 2.5.
Push the Start button on the keypad.
Check the Monitoring Menu and make sure
that the value of Output frequency. changes
according to the change of frequency
reference.
Push the Stop button on the keypad.
41
without motor
. Perform either
31-00108—07