Honeywell SmartVFD HVAC2 Applications Manual page 104

Table of Contents

Advertisement

Protections (Control panel: Menu PAR -> P12)
Code
Parameter
P12.1
Analog Input low
fault
P12.2
Under voltage fault
P12.3
Earth fault
P12.4
Output Phase Fault
P12.5
Stall protection
i
P12.6
Under load
i
protection
P12.7
Motor thermal
i
protection
Table 37. Protections.
Min
Max
0
4
1
2
0
3
0
3
0
3
0
3
0
3
104
Unit Default
ID
1
700
2
727
2
703
2
702
0
709
0
713
2
704
Note
= No action
0
1
= Alarm
2
= Alarm, preset alarm
frequency
3
= Fault: Stop function
4
= Fault: Coast
1 = No response (no fault
generated but drive still stops
modulation)
2 = Fault: Coast
0 = No action
1 = Alarm
2 = Fault: Stop function
3 = Fault: Coast
As parameter 12.3
As parameter 12.3
As parameter 12.3
As parameter 12.3
31-00108—07

Advertisement

Table of Contents
loading

Table of Contents