Table 62. SmartVFD HVAC2 technical data. (Continued)
Ambient
Ambient operating
conditions
temperature
Storage temperature -40 °F (-40 °C)...+158 °F (70 °C)
Relative humidity
Air quality:
- chemical vapours
- mech. particles
Altitude
Vibration:
EN60068-2-6
Shock
IEC 68-2-27
Enclosure class
Pollution degree
14 °F (-10 °C) (no frost)...+104/122 °F (+40/50 °C) (depends
on the unit size): rated loadability I
Side by side installation for MI1-3 it is always 104 °F (40 °C);
For IP21/Nema1 option in MI1-3 the maximum temparture
is also 104 °F (40 °C)
0...95% RH, non-condensing, non-corrosive, no dripping
water
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 3281 ft. (1000 m).
1% derating for each 328 ft. (100 m) above 3281 ft. (1000 m);
max. 6562 ft. (2000 m)
3...150 Hz
Displacement amplitude 1(peak) mm at 3...15.8 Hz Max
acceleration amplitude 1 G at 15.8...150 Hz
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
IP20 for MI1-3, IP21 for MI4-5.
With HVFDCDNEMA1xxx kit, IP21/NEMA1 for MI1-5.
PD2
184
N
31-00108—07