Local / remote
This parameter defines whether the control place
of the drive is remote (I / O or FieldBus) or local.
Remote Control
0 =
Local Control
1 =
The priority order of selecting control place is
1. PC control from Honeywell live operation
window
2. Loc / Rem button
3. Forced from I / O terminal
Frequency references (Control
panel: Menu PAR -> P3)
Remote control place frequency
reference selection
It defines the selected frequency reference source
when the drive is remote control. A second
reference source is programmable in par. 3.12.
=
4.
Preset speed 0
=
5.
Keypad reference
=
6.
Fieldbus Reference
=
7.
AI1
=
8.
AI2
=
9.
PID
=
10.
AI1+AI2
=
11.
Motor potentiometer
Preset speeds 0 - 7
Preset speed 0 is used as frequency reference
when P3.3 = 1.