Honeywell SmartVFD HVAC2 Applications Manual page 180

Table of Contents

Advertisement

Actual speed (output process data)
This is actual speed of the frequency converter.
The scaling is -10000...10000. The value is scaled
in percentage of the frequency area between set
minimum and maximum frequency.
Control word (input process data)
The three first bits of the control word are used to
control the frequency converter. By using control
word it is possible to control the operation of the
drive. The meanings of the bits of control word are
explained in the table below:
Table 61. Control word (input process data)
Bit
B0, RUN Stop
B1, DIR
Clockwise
B2, RST
Rising edge of this bit will reset active
fault
B5,
Normal
Quick
deceleration ramp
ramp
time
time
Speed reference (input process data)
This is the Reference 1 to the frequency converter.
Used normally as Speed reference. The allowed
scaling is 0...10000. The value is scaled in
percentage of the frequency area between the set
minimum and maximum frequencies.
180
Description
Value = 0
Run
Counter-
clockwise
Quick
deceleration
ramp time
Value = 1
31-00108—07