Honeywell SmartVFD HVAC2 Applications Manual page 36

Table of Contents

Advertisement

Table 13. Cable and fuse sizes for SmartVFD HVAC2, 380 - 480 V, 3~
Fuse
Frame Horsepower
[A]
MI1
.5-1HP
6
MI2
1.5-3HP
10
MI3
4-7.5HP
20
MI4
10-15HP
25
MI5
20-25HP
40
Table 14. Cable and fuse sizes for SmartVFD HVAC2, 600 V,3~
Fuse
Frame Horsepower
[A]
MI3
1-3HP
6
MI3
5HP
10
MI3
7.5HP
20
NOTE: To fulfill standard EN61800-5-1, the protective conductor should be at least 8 AWG Cu or 6
AWG Al. Another possibility is to use an additional protective conductor of at least the same
size as the original one.
Mains cable
Motor cable
Cu [AWG]
Cu [AWG]
3*16+16
3*16+16
3*16+16
3*16+16
3*14+14
3*14+14
3*10+10
3*10+10
3*6+6
3*6+6
Mains cable
Motor cable
Cu [AWG]
Cu [AWG]
3*16+16
3*16+16
3*16+16
3*16+16
3*14+14
3*14+14
Terminal cable size (min/max)
Main terminal
Earth terminal
[AWG]
[AWG]
1.5-4
16-12
1.5-4
16-12
16-10
16-10
17-6 Cu
17-6
14-1 Cu / Al
14-2
Terminal cable size (min/max)
Main terminal
Earth terminal
[AWG]
[AWG]
16-12
16-12
16-12
16-12
16-10
16-10
36
Control terminal
Relay terminal
[AWG]
20-16
20-16
20-16
20-16
20-16
20-16
20-16
20-16
20-16
20-16
Control terminal
Relay terminal
[AWG]
20-16
20-16
20-16
20-16
20-16
20-16
[AWG]
[AWG]
31-00108—07