Time Constant For Calculating The Adjusted Outside Temperature - Viessmann VITOTRONIC 300 Installation And Service Instructions Manual

For contractors. type cm1e, cc1e
Table of Contents

Advertisement

Parameters, Vitotronic 300
General, Vitotronic 300

06 Time constant for calculating the adjusted outside temperature

Display
1280 minutes
... Minutes
0B Set flow temperature for external demand
Display
70 °C
... °C
0C Differential temperature for raising the set flow temperature
Display
8 K
... K
12 Wireless outside temperature sensor
Display
Without wireless outside temperature sen-
sor
With wireless outside temperature sensor
Wireless outside temperature sensor not
used
13 Wireless base station
Display
Without
With
14 Fault message module 1
Display
Without
With
58
(cont.)
Value
06:128
06:1 to
06:199
!
Value
0B:70
0B:0 to
0B:127
Value
0C:8
0C:0 to
0C:40
Value
12:0
12:1
12:2
Value
13:0
13:1
Value
14:0
14:1
Explanations
Time constant for calculating the adjusted outside
temperature 21.3 h
Subject to the set value, the flow temperature is adjus-
ted quickly (low values) or slowly (high values) when
the outside temperature changes
1 step
10 min
Explanations
Limited by boiler-specific parameters
Explanations
The differential temperature is the value by which the
common flow temperature should be higher than the
highest currently required flow temperature of the
heating circuit with mixer.
Only in conjunction with heating circuits 2 and 3 with
mixer.
Explanations
Do not adjust
Explanations
Recognised automatically.
Explanations
Recognised automatically.