Control Strategies - Viessmann VITOTRONIC 300 Installation And Service Instructions Manual

For contractors. type cm1e, cc1e
Table of Contents

Advertisement

Cascade control
(cont.)

Control strategies

Condensing strategy
Benefit
Starting criterion
Shutdown criterion
Example (parameter "07:0" in the "Cascade" group)
Two-boiler system with modulating burners:
Boiler 1: 100 % rated heating output (base load set
to 33 %)
Boiler 2: 100 % rated heating output (base load set
to 33 %)
Start-up
100
66
33
0
100
33
0
200
150
100
33
0
Optimum utilisation of the condensing effect and long burner runtimes
Set parameter "07:0" in the "Cascade" group.
It is the aim of the condensing strategy to operate as many boilers as pos-
sible at the lowest output level.
An output statement causes the boilers to be started (parameter "08:1" in
the "Cascade" group).
An additional boiler will start if the current heat demand can also be cov-
ered by the currently active boilers plus the next boiler in the boiler se-
quence.
The boilers are shut down via a shutdown integral. If the shutdown integral
exceeds a limit set in parameter "0C" in the "Cascade" group, the last
started boiler is shut down.
Shutdown
t
System function description
100
66
33
0
100
33
0
200
150
100
33
0
t
137