Installation Of Outdoor Temperature Sensor - Viessmann KW10 Installation, Start-Up And Service Instructions Manual

Vitotronic 100 boiler control unit for modulating temperature heating systems
Table of Contents

Advertisement

Electrical Connections

Installation of Outdoor Temperature Sensor

Temperature
Resistance
ºF
ºC
-50
-46
490813
-45
-43
405710
-40
-40
336606
-35
-37
280279
-30
-34
234196
-25
-32
196358
-20
-29
165180
-15
-26
139402
-10
-23
118018
-5
-21
100221
0
-18
85362
5
-15
72918
10
-12
62465
15
-9
53658
12
To mount outdoor temperature sensor,
experience has shown that the north or
north-west outside wall of the building
is the best location. If, however, the
boiler is intended to supply heat to the
south side of the building only (split
piping system), the sensor must be
mounted on the south side.
The sensor must be mounted so that
water cannot infiltrate the sensor
housing.
Care must be taken to install the
sensor where it will not be affected by
heat sources such as windows or
ventilation openings. The sensor should
be installed far enough above the
ground to prevent accidental damage
or tampering. Operating temperature
range is -60 to 160 °F / -50 to 70 °C.
Total cable length from boiler to sensor
should not exceed 1000 ft. / 300 m if
18 gage wire is used. This sensor cable
should not be placed in direct contact
with line voltage.
In addition, the outdoor sensor must
not be covered with mortar, stucco,
paint or any form of coating or siding.
If the outside wall is finished after the
sensor is installed, the sensor should
be removed and placed on the finished
wall.
Temperature
Resistance
ºF
ºC
20
-7
46218
25
-4
39913
30
-1
34558
35
2
29996
40
4
26099
45
7
22763
50
10
19900
55
13
17436
60
16
15311
65
18
13474
70
21
11883
75
24
10501
80
27
9299
85
29
8250
Installation
1.Remove cover
2.Mount housing base
opening
The outdoor temperature sensor
must be surface-mounted on exterior
cladding - not encased in any way by
outside façade.
3.Affix wires to connectors
Wires are interchangeable.
4.Slip cover
a snap.
Do not paint cover.
Electrical connections
5.Connect the other end of the
two-conductor cable to terminals "1"
and "2" of the "1 / 3" plug (boiler
sensor plug). Wires are
interchangeable.
6.The outdoor sensor can be checked
by measuring resistance in respect to
current outdoor temperature.
Disconnect outdoor sensor from
control. Using an Ohmmeter,
measure resistance between the
sensor cable terminals. The expected
values are as follows:
Temperature
Resistance
ºF
ºC
90
32
7334
95
35
6532
100
38
5828
105
41
5210
110
43
4665
115
46
4184
120
49
3760
125
52
3383
130
54
3050
135
57
2754
140
60
2490
145
63
2255
150
66
2045
155
68
1857
.
1
(cable inlet
2
to bottom).
3
.
4
in place and affix with
1
Temperature
Resistance
ºF
ºC
160
71
1689
165
74
1538
170
77
1403
175
79
1281
180
82
1172
185
85
1073
190
88
983
195
91
903
200
93
829
205
96
763
210
99
703
215
102
648
220
104
598
225
107
553