Cascade control

Brief description
The common flow temperature is regulated by starting
or stopping the burners or by starting/stopping individ-
ual burner stages.
Operation is via 2 control modes:
Standalone control (see page 136)
Sequential control (see page 136)
Set common flow temperature
The set common flow temperature is determined from
the following parameters:
Set flow temperature for heating circuit 1 without
mixer, and heating circuits 2 and 3, each with mixer
Set flow temperature of further consumers
Set DHW temperature
External demands
Control range limits:
Upper control range limits:
Maximum system flow temperature limit (parameter
"02" in the "Cascade" group).
Lower control range limits:
Minimum system flow temperature limit (parameter
"01" in the "Cascade" group).
Common flow temperature control
110
A
80
D
8 K
+20
Outside temperature in °C
Fig. 42
Maximum flow temperature limit (parameter "02" in
A
the "Cascade" group)
B
Slope = 1.8 for heating circuit without mixer
Slope = 1.2 for heating circuit with mixer
C
Common flow temperature (at a differential tem-
D
perature = 8 K)
Lower common flow temperature
E
A control strategy is set for each control type:
Condensing strategy (see page 137)
Conventional boiler strategy 1 (see page 138)
Conventional boiler strategy 2 (see page 138)
Differential temperature:
The differential temperature can be set in parameter
"0C" in the "General" group.
Delivered condition 8 K.
The differential temperature is the value by which the
common flow temperature should be higher than the
highest currently required flow temperature of the
heating circuit with mixer.
System with only one heating circuit with mixer:
The common set flow temperature is regulated auto-
matically to 8 K above the set flow temperature of
the heating circuit with mixer.
System with heating circuit without mixer and heating
circuits with mixer:
The common set flow temperature operates in
accordance with its own heating curve. The differen-
tial temperature of 8 K towards the set flow tempera-
ture of the heating circuits with mixer is set at the
factory.
B
C
E
-20
System function description
135