Commissioning
Adjusting the heating curve
110
100
90
80
70
60
50
40
30
10
Fig. 35
Example for outside temperature
Underfloor heating system, slope 0.2 to 0.8
A
Low temperature heating system, slope 0.8 to 1.6
B
Heating systems with a boiler water temperature in
C
excess of 75 °C, slope greater than 1.6
Adjusting the set room temperature
Individually adjustable for each heating circuit.
The heating curve is offset along the set room temper-
ature axis. With the heating circuit pump logic function
enabled, the curve modifies the start and stop charac-
teristics of the heating circuit pump.
Standard set room temperature
110
26 °C
A
20 °C
C
-20
B
D
E
Fig. 36
Adjusting the standard set room temperature
from 20 to 26 °C
Boiler water temperature or flow temperature in °C
A
Outside temperature in °C
B
Set room temperature in °C
C
Heating circuit pump off
D
Heating circuit pump on
E
52
(cont.)
Slope
5
0
-5 -10 -15 -20
Outside temperature in °C
14 °C
−
1.8
1.6
C
1.4
1.2
1.0
B
0.8
0.6
0.4
A
0.2
-25
-30
Changing the standard set room temperature
Operating instructions
Reduced set room temperature
110
A
C
B -20
D
Fig. 37
Adjusting the reduced set room temperature
from 3 to 14 °C
Boiler water temperature or flow temperature in °C
A
Outside temperature in °C
B
Set room temperature in °C
C
Heating circuit pump off
D
Heating circuit pump on
E
14 °C
3 °C
E