Electrical connections

Connecting an AC burner

Pressure-jet oil/gas burner
The burner cables are included in the standard boiler
delivery.
Connect burner to DIN 4791.
Max. power consumption 6 (3) A
41
STB
TR
L1
N T1 T2 S3 B4
Fig. 23
To the control unit
A
To the burner
B
Plug terminal designations
L1
Phase via high limit safety cut-out to the burner
PE
Earth conductor to burner
N
Neutral conductor to burner
T1, T2 Control chain
S3
Burner fault terminal
B4
Hours run meter terminal
Signal flow direction:
Control unit
burner
Signal flow direction:
Burner
control unit
Plug equipment codes
fA
STB Control unit high limit safety cut-out
TR
Control unit temperature controller
Viessmann MatriX burner for Vitocrossal
The burner cables are included in the standard boiler
delivery.
Max. power consumption 6 (3) A
38
:
fA
:
H1
Burner fault signal
BZ
Hours run meter
90
BN
BK
BU
Fig. 24
To the control unit
A
To the burner
B
Plug terminal designations
T6, T8 Control chain burner stage 2 ON or modulation
controller Open
T6, T7 Control chain burner stage 2 OFF or modula-
tion controller Close
Signal flow direction:
Control unit
burner
Signal flow direction:
Burner
control unit
Colour coding to IEC 60757:
BK Black
BN Brown
BU Blue
Burner without plug
Fit the mating plug from Viessmann or from the burner
manufacturer. Connect the burner cables.
: