External functions
(cont.)
Function
External blocking boiler
Contact
Closed
Note
If all boilers are blocked or no other boiler
is ready for operation, the heating system
is not protected against frost.
Open
The boiler is enabled.
Parameter

Adding external boiler as last in boiler sequence

!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection must be potential-
free.
Function
Start the boiler externally as the last one in the boiler sequence
Control unit
Connection
Plug
1
143
B
A
B
Contact
Closed
This boiler is started last if the other boilers in the heating system cannot provide suffi-
cient heat.
Open
The boiler is integrated into the current boiler sequence.
Boiler is blocked.
Shut-off devices are closed.
The boiler circuit pump or shunt pump (if
installed) is switched off.
Vitotronic 300 (for assigned boilers)
Vitotronic 100
.2/
.3
aVD
aVD
A
2 3
Floating contact
Plug
of the control unit
aVD
Electrical connections
External system blocking
All boilers are blocked.
Shut-off devices are closed.
Note
There is no frost protection for the heating
system.
All boilers are enabled.
Set "42" (DE1), "43" (DE2) or "44" (DE3) in
the "General" group to 3 or 4.
33