B Set Flow Temperature For External Demand - Viessmann Vitotronic 11 CC1E Installation And Service Instructions Manual

Table of Contents

Advertisement

Parameter
General
(cont.)

0B Set flow temperature for external demand

Display
70 °C
... °C
14 Fault message module 1
Display
Without
With
15 Fault message module 2
Display
Without
With
16 Burner control unit connection
Display
Other
KM-BUS
CAN bus
1A Solar control unit
Display
Without
With Vitosolic 100
With Vitosolic 200
Solar control module, type SM1, without
auxiliary function
Solar control module, type SM1, with auxili-
ary function, e.g. central heating backup
1B Pump module PM1
Display
Without
With
20 Flow temperature sensor for low loss header
Display
Without
With
58
!
Value
Explanations
Limited by boiler-specific parameters
0B:70
0B:0 to
0B:127
Value
Explanations
14:0
14:1
Recognised automatically.
Value
Explanations
15:0
15:1
Recognised automatically.
Value
Explanations
16:0
Never adjust
16:1
16:2
Value
Explanations
1A:0
1A:1
1A:2
Recognised automatically.
1A:3
1A:4
Differential temperature control 2 with temperature
sensor
and
/
Value
Explanations
1 B:0
1 B:1
Recognised automatically.
Value
Explanations
20:0
20:1
Recognised automatically.