Connecting Actuators - Viessmann VITOTRONIC 300 Installation And Service Instructions Manual

For contractors. type cm1e, cc1e
Table of Contents

Advertisement

Connecting actuators

Extension connections for heating circuits 2 and 3, each with mixer
Plug
Component
M2/M3
Mixer motor, mixer extension kit
gS
Connections on the 230 V~ PCB
Plug
Component
One of the following functions:
gS
A1
Motorised butterfly valve, boiler
Mixing valve for boiler return temperature
control
Mixing valve, heat exchanger set
M
1~
52
Fig. 19
OPEN
CLOSE
Connecting a central fault message facility
Plug
Vitotronic 300: All system faults are transferred.
Vitotronic 100: Faults from the respective boiler are
transferred.
L
N
50
Fig. 20
Vitotronic 300
X
Vitotronic 300
X
X
X
Rated voltage
230 V~
Rated current
Max. 0.2 (0.1) A~
Runtime
5 to 199 s
Setting runtime
The runtime can be set by means of the following
parameters:
in conjunction with plug
"56" in the "General" group
"0F" in the "DHW" group
in conjunction with plug
"16" in the "Heating circuit..." group
Rated voltage
Rated current
Electrical connections
Vitotronic 100
Vitotronic 100
X
X
A1:
gS
gS
M2/M3:
230 V~
Max. 4(2) A~
31