Boiler, Vitotronic 300 - Viessmann VITOTRONIC 300 Installation And Service Instructions Manual

For contractors. type cm1e, cc1e
Table of Contents

Advertisement

Boiler, Vitotronic 300

Parameter values in bold are factory settings.
02 Burner type
!
Display
Single stage burner
Two-stage burner
Modulating burner
03 Boiler protection, gas/oil operation
Display
Gas operation
Oil operation
Resetting to gas not possible.
04 Switching hysteresis burner
Display
Switching hysteresis 4 K
ERB50 function
ERB80 function
05 Burner curve
!
Display
Linear burner curve
% of rated output at 1/3 of the modulation
range
Value
Explanations
02:0
02:1
02:2
!
Value
Explanations
03:0
03:1
Value
Explanations
Note
Factory setting, according to coding card
Only for single stage burner
04:0
04:1
04:2
Value
Explanations
Note
Factory setting, according to coding card
The burner curve varies depending on the type of
burner.
The burner curve shows the burner output (in %) in re-
lation to the opening angle of the butterfly valve (in
%).
See chapter "Matching the control unit to the modulat-
ing burner".
05:0
05:1 to
05:99
Parameters, Vitotronic 300
69

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 100

Table of Contents