REMKO WLT EC Series Operating And Installation Instructions page 42

Wall units in 2-conductor version with multifunctional control technology
Table of Contents

Advertisement

REMKO WLT EC series
Function logic (SW2)
The units can be used for numerous applications
and requirements. The settings in the table below
are possible using switch block SW2. It is generally
not necessary to change this switch block (excep-
tion S2)
SW2
Function logic
Use of a control valve
Use without a control
valve
Heating mode fan oper-
ation > 36 °C
Heating mode fan oper-
ation > 28 °C
Close-loop fan opera-
tion
Open-loop fan opera-
tion
Re-heat mode
fan not active
Re-heat mode
fan active
Fig. 35: DIP switch blocks SW1-SW3
42
S1
S2
S3
S4
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Unit configuration (SW3)
Adjusting this DIP switch provides the regulation
with specific key variables that are required for
safe control behaviour and optimised unit opera-
tion. Only the configuration specified for the rele-
vant unit is permitted to be used here, as this is the
only way to guarantee optimised control behaviour.
SW3
Unit type
S1
WLT 30 EC
ON
WLT 40 EC
OFF
WLT 50 EC
ON
WLT 60 EC
OFF OFF
WLT 80 EC
ON
WLT 90 EC
OFF
S2
S3
S4
S5
OFF OFF OFF OFF
ON
OFF OFF OFF
ON
OFF OFF OFF
ON
OFF OFF
OFF
ON
OFF OFF
ON
ON
OFF OFF