Internal Network - REMKO WLT EC Series Operating And Installation Instructions

Wall units in 2-conductor version with multifunctional control technology
Table of Contents

Advertisement

9

Internal network

Up to 32 units can be operated at the same time
thanks to the parallel connection via a bus line
(accessory). The units can access this network
(internal network) at the same time.
The network can have one leading unit (master)
and up to 31 following units (slave).
The units are connected together via a two-core,
shielded bus line.
The minimum cross section is 1.0 mm
imum line length of 500 m in the network (observe
the polarity!).
The end of the network must be marked by the
plugged in jumper JP1. The addresses are
assigned by adjusting the DIP switch block SW1
(see the "Configuration" chapter).
Network with infrared remote controls
n
The standard infrared remote control operates
a master unit. All slave units are set according
to the programming.
8
9
10
11
JP1
Fig. 36: Internal network wiring diagram
2
with a max-
12
13 14
n
The infrared remote control or the cabled
remote control (accessory) can be used for
user-specific operation of an individual slave
unit.
Implementation
n
Address assignment for the units is carried out
by changing the DIP switch settings for DIP
switch block SW1.
Network with cabled remote controls
n
The cabled remote control that is available as
an accessory operates a master unit. All slave
units with cabled remote control can be pro-
grammed individually from the master unit
directly or as a complete group.
n
The cabled remote control (accessory) can be
used for user-specific operation of an individual
slave unit.
Implementation
n
The addresses for the master and slave units
are assigned by configuring the cabled remote
control (see separate installation instructions).