DURADRIVE Drive Controllers
XE1, Protective conductor connections for mains
Illustration
Tightening torque
Connection cross section
DOK-DURADR-HDC01.1****-PR02-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Technical description of connector
See page 4-21: "A look at the drive controller and connector
designations".
Design
Type
screw-in connection
Fig. 4-113: Design
min. tightening torque
Fig. 4-114: Tightening torque
Cross section
single wire
[mm²]
--
Fig. 4-115: Connection cross section
XE1, protective conductor connection for mains
DANGER
DURADRIVE HDC01.1 Drive Controller
No. of pins
1
[Nm]
2.5
Max. connectable
cross section
in mm²
25
Personal danger caused by large leakage
current!
⇒ The DURADRIVE drive controller is equipped with
an integrated power line filter. In order to prevent
danger, the connection cross section of the ground
wire connector XE1, in principle, must be at least
10 mm² (EN 50178/1998, section 5.3.2.1).
4-63
Design
screw-in connection for
ring terminals M5
max. tightening torque
[Nm]
3.0
Max. cross section
in AWG
gauge no.:
--