TIM 4R-IE
Cable length
Power supply
Current consumption
Power loss
Backup battery (optional) for message memory
and hardware clock
Clock
Permitted ambient conditions
Construction
Degree of protection
Configuration
SINAUT ST7 station control system
System Manual, 09/2016, C79000-G8976-C178-10
RS-232
RS-485
RJ-45
From backplane bus
From 24 V DC
Battery type
Voltage / capacity
Current consumption during backup
Leakage current
Hardware clock (real-time clock)
Buffered
Deviation per day
Operating temperature
Transport/storage temperature
Relative humidity
Module format
Dimensions (W x H x D) in mm
Weight
Software for PG
TD7 software for CPU (optional)
Storage of TIM configuration data
Technical specifications
6.2 Technical specifications of the TIM 4R-IE
max. 6 m
max. 30 m
max. 10 m
24 V DC; min. 20.4 V; max. 28.8 V
maximum 200 mA
typically 150 mA, max. 170 mA
typically 4.6 W
Lithium battery 6ES7 971-0BA00
Type Tadiran SL-306, cell type AA
3.6 V nom. / 2.3 Ah
typically 100 μA, max. 160 μA
typically 15 μA
yes
yes (with backup battery)
max. 4 s
0 °C to +60 °C
-40 °C to +70 °C
Max. 95 % at +25 °C
Compact module for S7-300, double width
80 x 125 x 120
Approx. 400 g
IP 20
SINAUT ST7 configuration software
for PG
SINAUT TD7 block library for CPU
Storage:
on internal TIM flash memory
on TIM in optional C-PLUG
on MMC of the S7-300-CPU, if TIM fitted
in S7-300 controller