The selection of the standard dedicated line profile not only depends on the required
transmission speed but also on the interface to be used, the RS-232 or the RS-485 interface.
Standard dedicated line profiles 8 to 14 are only suitable for use with the RS-232 interface. If
you require the RS-485 interface, the user-configurable dedicated line profile 15 must be set
and configured. Profile 15 can, however, also be used with the RS-232 interface.
Loudspeaker ON or OFF
The MD3 modem is equipped with a loudspeaker. The loudspeaker allows you to hear all the
signal tones during the connection phase and during data transmission. The loudspeaker
can be turned on for test purposes or for normal operation.
Table 5- 33
Loudspeaker
Turned off
Turned on
Modem reset
If the configuration of the modem is unclear, you can reset to the factory default settings.
When you reset the modem, all 16 standard profiles are reset to the default setting.
Procedure:
1. Power supply OFF
2. Set switch SW2.7 to ON
3. Turn the power supply ON and then wait at least 10 seconds until the DCD LED lights up.
SINAUT ST7 station control system
System Manual, 09/2016, C79000-G8976-C178-10
Installation and commissioning of the modems and routers
Meaning
33600 bps (buffered)
(suitable only for RS-232 port)
AT mode
Freely configurable
(also suitable for RS-485 port)
Setting the loudspeaker
5.7 Analog dial-up modem MD3
Setting on DIL switch
Setting on DIL switch