Operation
8.3 Operation via the AOP30 operator panel
Resetting the fan runtime
In this menu, you can reset the fan counter. The fan counter must be reset after a fan
replacement.
1. Press the <▼> function key to select the "Reset runtime" row.
2. Confirm the selection with <OK>. The reset of the fan runtime also clears alarm A30042.
8.3.3.6

Commissioning / Service - AOP settings

Commissioning /Service / AOP settings menu structure
Figure 8-12
Calling up AOP settings
1. Press the <<MENU>> key.
2. Press the <▼> function key to select the "Commissioning/Service" row. Press the <OK>
3. Press the <▼> function key to select the "AOP settings" row. Press the <OK> function key
4. Press the ▲ or ▼ function key to select the desired setting. Press the <OK> function key to
* The "Extended settings" menu appears only when the "special access" access level is
selected.
128
Commissioning /Service / AOP settings menu structure
function key to confirm the selection.
to confirm the selection.
confirm the selection.
SINAMICS GM150 6SL3810-2LN31-8AA2
Operating Instructions Rev.201910281332 EXAMPLE