3.6 Description of options
the braking resistor with a temperature monitoring. Wire the temperature monitoring so that the
drive shuts down when triggered.
The braking resistor and cabling are required to meet the following requirements in relation to
inductance L:
The time constant L/R must not exceed the value 20 µs. L must be smaller than R x 20 μs.
Note
The signal cable to the temperature monitor and the power cable are not included in the scope
of supply.
See also
Braking Module (option L72) (Page 52)
56