2. Introduction to the VLT AQUA Drive
2.10.4. EMC Immunity
In order to document immunity against interference from electrical phenomena, the following
immunity tests have been performed on a system consisting of an adjustable frequency drive (with
2
options, if relevant), a shielded control cable and a control box with potentiometer, motor cable
and motor.
The tests were performed in accordance with the following basic standards:
See following EMC immunity form.
VLT AQUA; 200-240 V, 380-480 V
Basic standard
Acceptance criterion
Line
Motor
Brake
Load sharing
Control wires
Standard bus
Relay wires
Application and serial com-
munication options
LCP cable
External 24 V DC
Enclosure
AD: Air Discharge
CD: Contact Discharge
CM: Common mode
DM: Differential mode
1. Injection on cable shield.
2.2: Immunity
34
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD)
electrostatic discharges from human beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation,
amplitude modulated
Simulation of the effects of radar and radio communication
equipment as well as mobile communications.
EN 61000-4-4 (IEC 61000-4-4): Electrical interference
caused by switching with a contactor, relays, or similar devices.
EN 61000-4-5 (IEC 61000-4-5): Surge transients
e.g., by lightning strikes near installations.
EN 61000-4-6 (IEC 61000-4-6): RF Common mode
radio-transmitting equipment connected to connection cables.
Burst
IEC 61000-4-4
B
4 kV CM
4 kV CM
4 kV CM
4 kV CM
2 kV CM
2 kV CM
2 kV CM
2 kV CM
2 kV CM
2 kV CM
MG.20.N2.22 - VLT
Simulation of transients caused,
Surge
ESD
Radiated electromagnetic
IEC 61000-4-5
IEC
61000-4-2
IEC 61000-4-3
B
B
2 kV/2 Ω DM
4 kV/12 Ω CM
4 kV/2 Ω
1)
4 kV/2 Ω
1)
4 kV/2 Ω
1)
2 kV/2 Ω
1)
2 kV/2 Ω
1)
2 kV/2 Ω
1)
2 kV/2 Ω
1)
1)
2 kV/2 Ω
0.5 kV/2 Ω DM
1 kV/12 Ω CM
8 kV AD
6 kV CD
®
is a registered Danfoss trademark.
VLT
®
AQUA Drive Design Guide
Simulation of
Simulation of interference
Simulation of the effect from
RF common
field
mode voltage
IEC 61000-4-6
A
A
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V/m