6. Warnings and Alarms
Alarm Word Extended Status Word
Bit
0
1
2
3
4
5
6
7
8
9
10
6
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Table 6.3: Description of Alarm Word, Warning Word and extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or
optional fieldbus for diagnose. See also par. 16-90 - 16-94.
WARNING 1, 10 Volts low:
The 10 V voltage from terminal 50 on the con-
trol card is below 10 V.
Remove some of the load from terminal 50, as
the 10 V supply is overloaded. Max. 15 mA or
minimum 590 Ω.
WARNING/ALARM 2, Live zero error:
The signal on terminal 53 or 54 is less than
50% of the value set in par. 6-10, 6-12, 6-20,
or 6-22 respectively.
WARNING/ALARM 3, No motor:
No motor has been connected to the output of
the frequency converter.
126
Hex
Dec
Alarm Word
00000001
1
Brake Check
00000002
2
Pwr. Card Temp ServiceTrip,
00000004
4
Earth Fault
00000008
8
Ctrl.Card Temp ServiceTrip,
00000010
16
Ctrl. Word TO
00000020
32
Over Current
00000040
64
Torque Limit
00000080
128
Motor Th Over
00000100
256
Motor ETR Over
00000200
512
Inverter Overld.
00000400
1024
DC under Volt
00000800
2048
DC over Volt
00001000
4096
Short Circuit
00002000
8192
Inrush Fault
00004000
16384
Mains ph. Loss
00008000
32768
AMA Not OK
00010000
65536
Live Zero Error
00020000
131072
Internal Fault
00040000
262144
Brake Overload Fans error
00080000
524288
U phase Loss
00100000
1048576
V phase Loss
00200000
2097152
W phase Loss
00400000
4194304
Fieldbus Fault
00800000
8388608
24 V Supply Low
01000000
16777216
Mains Failure
02000000
33554432
1.8V
Low
04000000
67108864
Brake Resistor
08000000
134217728
Brake IGBT
10000000
268435456
Option Change
20000000
536870912
Drive Initialized
40000000
1073741824 Safe Stop (A68) PTC
80000000
2147483648 Mech. brake low Dangerous
MG.33.U1.02 - VLT
Alarm Word 2 Warning Word
ServiceTrip,
Brake Check
Read/Write
Pwr. Card Temp
(reserved)
ServiceTrip,
Earth Fault
Typecode/
Sparepart
Ctrl.Card Temp
(reserved)
ServiceTrip,
Ctrl. Word TO
(reserved)
Over Current
Torque Limit
Motor Th Over
Motor ETR Over
Inverter Overld.
DC under Volt
DC over Volt
DC Voltage Low
DC Voltage High
Mains ph. Loss
No Motor
Live Zero Error
KTY error
10V Low
Brake Overload
ECB error
Brake Resistor
Brake IGBT
Speed Limit
Fieldbus Fault
24V Supply Low
Mains Failure
Supply
Current Limit
Low Temp
Voltage Limit
Encoder loss
Output freq. lim.
1
Safe
Safe Stop (W68)
Stop (A71)
Extended
Failure (A72)
Word
WARNING/ALARM 4, Mains phase loss:
A phase is missing on the supply side, or the
mains voltage imbalance is too high.
This message also appears in case of a fault
in the input rectifier on the frequency convert-
er.
Check the supply voltage and supply currents
to the frequency converter.
WARNING 5, DC link voltage high:
The intermediate circuit voltage (DC) is higher
than the over-voltage limit of the control sys-
tem. The frequency converter is still active.
®
is a registered Danfoss trademark
®
VLT
Automation Drive FC 300
Operating Instructions High Power
Warning
Extended
Word 2
Status Word
Ramping
AMA Running
Start CW/CCW
Slow Down
Catch Up
Feedback High
Feedback Low
Output
Current
High
Output
Current
Low
Output Freq High
Output Freq Low
Brake Check OK
Braking Max
Braking
Out
of
Speed
Range
OVC Active
AC Brake
KTY Warn Password
Time-
lock
Fans
Password Protec-
Warn
tion
ECB Warn
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
PTC
1
Unused
Safe Stop
(W71)
Status
Unused

Advertisement

Table of Contents
loading

Table of Contents