2.1.8. Safe Stop Installation

To carry out an installation of a Catego-
ry 0 Stop (EN60204) in conformity with
2
Safety Category 3 (EN954-1), follow
these instructions:
1.
2.
The illustration below shows a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN
954-1). The circuit interrupt is caused by an opening door contact. The illustration also shows how
to connect a non-safety related hardware coast.
Illustration 2.2: Illustration of the essential aspects of an installation to achieve a Stopping Category 0 (EN
60204-1) with safety Category 3 (EN 954-1).

2.1.9. IT Mains

Par. 14-50
the RFI filter to ground. If this is done it will reduce the RFI performance to A2 level.
10
The bridge (jumper) between Termi-
nal 37 and 24 V DC must be re-
moved. Cutting or breaking the
jumper is not sufficient. Remove it
entirely to avoid short-circuiting. See
jumper on illustration.
Connect terminal 37 to 24 V DC by a
short-circuit protected cable. The 24
V DC voltage supply must be inter-
ruptible by an EN954-1 Category 3
circuit interrupt device. If the inter-
rupt device and the frequency con-
verter are placed in the same instal-
lation panel, you can use an
unscreened cable instead of a
screened one.
RFI 1
can on FC 102/202/302 be used to disconnect the internal RFI capacitors from
MG.33.U1.02 - VLT
Operating Instructions High Power
Illustration 2.1: Bridge jumper between terminal
37 and 24 VDC
®
is a registered Danfoss trademark
®
VLT
Automation Drive FC 300