General Specifications - Danfoss VLT Automation Drive FC 300 Operating Instructions Manual

Hide thumbs Also See for VLT Automation Drive FC 300:
Table of Contents

Advertisement

®
VLT
Automation Drive FC 300
Operating Instructions High Power

5. General Specifications

Mains supply (L1, L2, L3):
Supply voltage
Supply voltage
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ) near unity
Switching on input supply L1, L2, L3 (power-ups) ≥ 11 kW
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS sym-
metrical Amperes, 500/600/690 V maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Ramp times
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
Starting torque (Variable torque)
Overload torque (Variable torque)
*Percentage relates to the nominal torque.
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) Min. pulse width
Input resistance, R
Safe stop Terminal 37
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Nominal input current at 24 V
Nominal input current at 20 V
Input capacitance
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
1) Terminals 27 and 29 can also be programmed as output.
2)
2)
i
3)
(Terminal 37 is fixed PNP logic):
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
5. General Specifications
FC 302: 380-500 V ±10%
FC 302: 525-690 V ±10%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
maximum 1 time/ 2 min.
over-voltage category III/pollution degree 2
0 - 100% of supply voltage
0.01 - 3600 sec.
maximum 160% for 60 sec.
maximum 180% up to 0.5 sec.
maximum 160% for 60 sec.
maximum 110% for 60 sec.
maximum 110% for 60 sec.
18, 19, 27
50/60 Hz
(> 0.98)
5
0 - 800 Hz
Unlimited
*
*
*
*
4 (6)
1)
, 29, 32, 33,
PNP or NPN
0 - 24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
0 - 110 kHz
4.5 ms
approx. 4 kΩ
0 - 24 V DC
< 4 V DC
>20 V DC
50 mA rms
60 mA rms
400 nF
107