Danfoss VLT Automation Drive FC 300 Operating Instructions Manual page 111

Hide thumbs Also See for VLT Automation Drive FC 300:
Table of Contents

Advertisement

®
VLT
Automation Drive FC 300
Operating Instructions High Power
Surroundings:
Enclosure
Vibration test
Max. relative humidity
Aggressive environment (IEC 60068-2-43
Ambient temperature
1) For high ambient temperature, see special conditions in the Design Guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Derating for high altitude, see special conditions in the Design Guide
EMC standards, Emission
EMC standards, Immunity
See section on special conditions in the Design Guide
Protection and Features:
5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
1)
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips if the
temperature reaches a predefined level. An overload temperature cannot be reset until
the temperature of the heatsink is below the values stated in the tables on the following
pages (Guideline - these temperatures may vary for different power sizes, enclosures
etc.).
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending
on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips
if the intermediate circuit voltage is too low or too high.
The frequency converter constantly checks for critical levels of internal temperature, load
current, high voltage on the intermediate circuit and low motor speeds. As a response
to a critical level, the frequency converter can adjust the switching frequency and/ or
change the switching pattern in order to ensure the performance of the drive.
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
5. General Specifications
IP 21/ Type 1, IP 54/ Type 12
Max. 50 °C (24-hour average maximum 45 °C)
EN 61800-3, EN 61000-6-3/4, EN 55011
EN 61800-3, EN 61000-6-1/2,
1.0 g
class H
5
2
0 °C
- 10 °C
-25 - +65/70 °C
1000 m
5
61000-4-6
111