NEC Power-Limited Wiring Requirements for Maximal77D:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet . All power-limited
circuit wiring must remain at least 0 .25" away from any non power-limited circuit wiring . Furthermore, all
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits . One such example of this is shown below . Your specific application may require different conduit
knockouts to be used . Any conduit knockouts may be used . For power-limited applications use of conduit is
optional . All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute) .
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 8a).
Fig. 8
Optional Battery
Enclosure
(non power-limited)
Input
115VAC, 60Hz
(non power-limited)
Fig. 8a
Incorrect Wire
Handling
Insulation
Solid Copper
Conductors
Maximal11D/Maximal33D/Maximal55D/Maximal77D/Maximal75D Access Power Controllers (PTC)
Supervisory
Connections
(power-limited)
Correct Wire
Handling
External
Jacketed
Shield
Wire
Pull back
external jacketed
shield approx. 1/2".
External UL Listed Power-
Limited, Access Control
Power Supply
12 to 24VAC or DC
Battery
Connections
(non power-limited)
ACM8CB
outputs
(power-
limited)
- 15 -