MaximalFDV Series Overview: Altronix MaximalFDV Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input into sixteen (16) independently controlled 12VDC or 24VDC PTC protected outputs. The outputs are activated by an open col- lector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc.
eFlow Power Supply/Charger: • Input: 220VAC (working range 198VAC - 256VAC), 50/60Hz. • For output voltage and supply current refer to MaximalFDV series Configuration Chart, pg. 3. • Auxiliary output rated @ 1A (unswitched). • Overvoltage Protection. • Built-in charger for sealed lead acid or gel type batteries. •...
Page 5
eFlow Auxiliary outputs (unswitched): For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX –] (Fig. 3, pg. 9). 7. Input trigger options (Fig. 2, pg. 8): (a) Normally Open [NO] input trigger: Inputs 1-8 are activated by normally open or open collector sink inputs.
Maintenance: Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup. Please follow the appropriate procedure below: Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect.
Access Power Controller Terminal Identification: Terminal Legend Function/Description 12VDC or 24VDC from power supply/charger (factory connected). – Power + These terminals are paralleled to the [– Control +] terminals. These terminals are paralleled to the [– Power +] terminals. These terminals can be connected to an external access control power supply to provide –...
Fig. 3 Maximal3FDV, Maximal5FDV, and Maximal7FDV. Tamper Switch Wire Ground Lug Strap (from Enclosure to Door) Power Supply Board AC FAIL BAT FAIL AC DELAY SHUTDOWN 5A 250V 1 min. enable TRIGGER EOL NC C NO NC C NO + AUX – 2 hr.
NEC Power-Limited Wiring Requirements: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ- ent conduits.
19” (482.6mm) Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. MEMBER IIMaximal3FDV/5FDV/7FDV Series G30R...