Altronix Maximal Series Installation Manual
Altronix Maximal Series Installation Manual

Altronix Maximal Series Installation Manual

Access power controllers, 12vdc 5/9/9.4 amp or 24vdc 5.4 amp. sixteen 16 fuse protected non power-limited outputs
Hide thumbs Also See for Maximal Series:

Advertisement

Series
Access Power Controllers
Installation Guide
Models Include:
Maximal3
- 12VDC @ 5 amp or 24VDC @ 5.4 amp.
- Sixteen (16) fuse protected non power-limited outputs.
Maximal5
- 12VDC @ 9 amp.
- Sixteen (16) fuse protected non power-limited outputs.
Maximal7
- 24VDC @ 9.4 amp.
- Sixteen (16) fuse protected non power-limited outputs.
Altronix Corp.
140 58th St. Brooklyn, NY
More than just power.
TM
Rev. SF110912

Advertisement

Table of Contents
loading

Summary of Contents for Altronix Maximal Series

  • Page 1 - 12VDC @ 9 amp. - Sixteen (16) fuse protected non power-limited outputs. Maximal7 - 24VDC @ 9.4 amp. - Sixteen (16) fuse protected non power-limited outputs. Altronix Corp. 140 58th St. Brooklyn, NY More than just power. Rev. SF110912...
  • Page 2: Table Of Contents

    Table of Contents: Maximal Series Overview ....................3 Maximal Series Configuration Chart................3 Maximal Series Features ....................3 Maximal Installation Instructions .................. 4-5 Maintenance ........................5 Power Supply Board LED Diagnostics ................5 Access Power Controller LED Diagnostics ..............6 Power Supply Board Terminal Identification ..............
  • Page 3: Maximal Series Overview

    The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs. All interconnecting equipment must be UL Listed. Maximal Series Configuration Chart: UL File # BP6714 12VDC @ 5 amp...
  • Page 4: Maximal Installation Instructions

    Maximal Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. Power Supply Board LED Diagnostics (pg. 5) Access Power Controller LED Diagnostics (pg.
  • Page 5: Maintenance

    (c) FACP Signaling Circuit input trigger: Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper J3 must be cut (Fig.
  • Page 6: Access Power Controller Led Diagnostics

    Power Supply Board LED Diagnostics (cont’d): Red (Bat) Battery Status Normal operating condition. Battery fail/low battery. Access Power Controller LED Diagnostics: LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized. Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition). Power Supply Board Terminal Identification: Terminal Function/Description...
  • Page 7: Power Supply Board Stand-By Battery Specifications

    Power Supply Board Stand-by Battery Specifications: Altronix 20 Min. of 4 hr. of 24 hr. of Power Supply Board Battery Model: Backup Backup Backup AL600ULXB 12VDC/40AH* 5.0 amp Maximal3 (Refer to Fig. 1a, pg. 7 for Switch 24VDC/40AH* 5.4 amp 0.7 amp...
  • Page 8: Access Power Controller Typical Application Diagram

    Access Power Controller Typical Application Diagram (for each ACM8): Fig. 2 Fig. 2a KEYPAD ACCESS CONTROL PANEL PUSH FACP BUTTON FACP Dry Form "C" (Fire OUTPUT Output Alarm RELAY Control Panel) IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND...
  • Page 9: Maximal3 And Maximal5 Battery Hookup And Tamper Switch Installation

    Fig. 3 Maximal3 Tamper Switch Maximal5 Maximal5 Wire Strap (from Power Supply Board Enclosure to Door) BAT FAIL AC FAIL NO C NC NO C NC 115VAC Input Line Neutral 60 Hz. Earth Ground *12VDC operation: For 12VDC operation only a single battery is needed. Connect red battery lead to terminal marked [+ BAT] and to the [positive (+)] terminal of the...
  • Page 10: Maximal7 Battery Hookup And Tamper Switch Installation

    Fig. 4 Maximal7 Tamper Switch Power Supply Board BAT FAIL AC FAIL NC C NO NC C NO AC DELAY 115VAC Input Line Neutral 60 Hz. Earth Ground Optional Optional 12VDC Battery** 12VDC Battery** **24VDC operation: Connect two (2) 12VDC batteries in series Fig.
  • Page 11: Nec Power-Limited Wiring Requirements For Maximal3

    NEC Power-Limited Wiring Requirements for Maximal3: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
  • Page 12: Nec Power-Limited Wiring Requirements For Maximal5

    NEC Power-Limited Wiring Requirements for Maximal5: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
  • Page 13: Nec Power-Limited Wiring Requirements For Maximal7

    NEC Power-Limited Wiring Requirements for Maximal7: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
  • Page 14: Facp Hook-Up Diagrams

    FACP Hook-up Diagrams: Fig. 8 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): JUMPER J3 FACP SIGNAL CIRCUIT OUTPUT EOL FROM FACP SIGNAL OUTPUT CIRCUIT Fig. 9 Normally Open - Non-Latching FACP Fig. 10 Normally Open FACP Latching trigger input trigger input: with reset: (This output has not been evaluated by UL)
  • Page 15: Enclosure Dimensions

    Enclosure Dimensions (H x W x D approx.): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm) 19” (482.6mm) 2” 2” 4” 7” 4” (50.8mm) (50.8mm) (101.6mm) (177.8mm) (101.6mm) 6.25” (158.75mm) 19” 1.25” (482.6mm) 1.25” 0.85” 0.85” (31.75mm) 8.9” 8.4”...
  • Page 16 Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. MEMBER IIMaximal3/5/7 Series F06N - 16 - Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused)