- Power Supply 1: - Power Supply 1: 12VDC @ 10A. 24VDC @ 10A. - Power Supply 2: - Power Supply 2: 24VDC @ 10A. 24VDC @ 10A. Altronix Corp. 140 58th St. Brooklyn, NY More than just power. Rev. ME102512...
12VDC/12AH batteries. All interconnecting equipment must be UL Listed. MaximalE Series Configuration Chart: Altronix Output Voltage Options Model Number Power Supply 1 Power Supply 2 AL400ULXB2 AL400ULXB2 Altronix Corp. 140 58th St. Brooklyn, NY 12VDC @ 4A 12VDC @ 4A Maximal11E 7.0A 5A/250V 15A/32V 12VDC @ 4A...
MaximalE Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. Power Supply Board Terminal Identification (pg. 5) Power Supply Stand-by Battery Specifications (pg.
Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. + DC – Refer to Maximal Series Configuration Chart, pg. 3. Indicates loss of AC power. To meet with UL requirements it is mandatory to connect visual notification AC FAIL devices, connecting audible notification devices is optional.
Power Supply Board LED Diagnostics: Power Supply Status Red (DC) Green (AC) Normal operating condition. Loss of AC. Stand-by battery supplying power. No DC output. Short circuit or thermal overload condition. No DC output. Loss of AC. Discharged battery. Red (Bat) Battery Status Normal operating condition.
Fig. 2 Tamper Switch Fig. 2a Power Supply Board Power Supply Board [BAT] Terminal Layout for: AL1024ULXB2 AC FAIL BAT FAIL NO C NC NO C NC Line Neutral Power Supply Board Power Supply Board [DC] BAT FAIL AC FAIL 115VAC NO C NC NO C NC...
NEC Power-Limited Wiring Requirements for Maximal11E: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
NEC Power-Limited Wiring Requirements for Maximal13E: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
NEC Power-Limited Wiring Requirements for Maximal33E, Maximal35E, and Maximal55E: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
NEC Power-Limited Wiring Requirements for Maximal37E and Maximal75E: Power-limited and non power- limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
NEC Power-Limited Wiring Requirements for Maximal77E: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Enclosure Dimensions (H x W x D approximate) 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm) 19” (482.6mm) 2” 4” 7” 4” 2” (50.8mm) (101.6mm) (177.8mm) (101.6mm) (50.8mm) 6.25” (158.75mm) 19” 1.25” (482.6mm) 1.25” 0.85” 0.85” (31.75mm) 8.9” 8.4”...
Page 14
Notes: - 14 - Maximal Expandable Power Systems...
Page 15
Notes: Maximal Expandable Power Systems - 15 -...
Page 16
Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A. IIMaximalE Series E27P MEMBER - 16 - Maximal Expandable Power Systems...
Need help?
Do you have a question about the Maximal series and is the answer not in the manual?
Questions and answers