Saving The Commissioning Settings - DeDietrich AMC Pro 45 Service Manual

Control panel & high efficiency wall-hung gas boiler
Hide thumbs Also See for AMC Pro 45:
Table of Contents

Advertisement

Tab.20
Load tests in the chimney sweep menu
Change load test mode
Off
MinimumPower
MaximumPowerCH
MaximumPowerDhw
Tab.21
Load test settings
Load Test menu
ChimneyModeStatus
System Flow Temp
T return
Actual fan RPM
Actual flame current
Fan RPM Max CH
Fan RPM Min
Fan RPM Start
Fig.22
Full load test
Fig.23
Part load test
7725087 - v.01 - 06062019
Settings
No test
Part load test
Full load test for Central Heating mode
Full load test for Central Heating + Domestic Hot Water mode
Settings
Select the load test to start the test.
Read the central heating flow temperature
Read the central heating return temperature
Read the actual fan speed
Read the actual flame current
Adjust the maximum fan speed during Central Heating mode
Adjust the minimum fan speed during Central Heating + Domestic Hot Water mode
Adjust the start fan speed
Performing the full load test
1. Select the tile [
2. Select the test MaximumPowerCH.
A Change load test mode
B MaximumPowerCH
A
3. Check the load test settings and adjust if necessary.
B
AD-3000941-02
Performing the part load test
1. If the full load test is still running, press the
load test mode.
2. If the full load test was finished, select the tile [
chimney sweep menu.
A Change load test mode
B MinimumPower
A
3. Select the MinimumPower test in the menu Change load test mode.
4. Check the load test settings and adjust if necessary.
5. End the part load test by pressing the
B
AD-3000941-02
6.3.2
You can save all current settings on the control panel. These settings can
be restored if necessary, for example after replacement of the control unit.
1. Press the
].
The Change load test mode menu appears.
The full load test starts. The selected load test mode is shown in the
menu and the icon
appears in the top right of the screen.
Only the parameters shown in bold can be changed.
The part load test starts. The selected load test mode is shown in
the menu and the icon
Only the parameters shown in bold can be changed.
The message Running load test(s) stopped! is displayed.

Saving the commissioning settings

button.
6 Installer instructions
button to change the
] to restart the
appears in the top right of the screen.
button.
AMC Pro
23