Changing The Domestic Hot Water Temperature Temporarily; Resetting Or Restoring Settings; Resetting The Configuration Numbers Cn1 And Cn2; Carrying Out An Auto-Detect For The Can Matrix - DeDietrich AMC Pro 45 Service Manual

Control panel & high efficiency wall-hung gas boiler
Hide thumbs Also See for AMC Pro 45:
Table of Contents

Advertisement

Fig.26
Version information
6.5

Resetting or restoring settings

Fig.27
Configuration numbers
A
11:20
...
.....
.... ......
.... ...... ....
.......
B
............ ....... ....... ....
......... ... .............. ...... .. .....
.......
C
...
.
...
.
........
7725087 - v.01 - 06062019
A
B
AD-3000936-01
6.4.4
When the timer program is active with a reduced domestic hot water
temperature, you can temporarily increase the hot water temperature for
e.g. testing of the hot water production.
You can delete or abort the temporary overwrite by selecting Reset.
6.5.1
The configuration numbers must be reset when indicated by an error
message or when the control unit has been replaced. The configuration
numbers can be found on the data plate of the appliance.
AD-3001385-01
6.5.2
When a control board has been replaced or removed from the boiler, this
function must be used to detect all devices connected to the CAN bus.
6.5.3
This option is only available when the commissioning settings were saved
on the control panel and allows you to restore these settings.
3. Select the appliance, control board or any other device you want to
view.
A Select the appliance, control board or device
B List of information
4. Select the information you want to view.
Changing the domestic hot water temperature
temporarily
1. Press the
button.
2. Select Installation Setup > Internal DHW > Hot water boost.
3. Select Duration of temporary overwrite .
4. Set the duration in hours and minutes.
The hot water temperature is increased to the DHW comfort
setpoint.

Resetting the configuration numbers CN1 and CN2

A Select the control unit
B Extra information
C Configuration numbers
1. Press the
button.
2. Select Advanced Service Menu > Set Configuration Numbers.
3. Select the control unit you want to reset.
4. Select and change the CN1 setting.
5. Select and change the CN2 setting.
6. Select Confirm to confirm the changed numbers.

Carrying out an auto-detect for the CAN matrix

1. Press the
button.
2. Select Advanced Service Menu > Auto Detect.
3. Select Confirm to carry out the auto-detect.

Restoring the commissioning settings

1. Press the
button.
2. Select Advanced Service Menu > Revert commissioning settings.
3. Select Confirm to restore the commissioning settings.
6 Installer instructions
AMC Pro
25