Table of Contents

Advertisement

PXC Compact Series
Technical Reference Manual
145-172
2018-09-25
Restricted
Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens PXC-16 Compact

  • Page 1 PXC Compact Series Technical Reference Manual Building Technologies 145-172 2018-09-25 Restricted...
  • Page 2 Copyright Notice Notice Document information is subject to change without notice by Siemens Industry, Inc. Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Industry, Inc.
  • Page 3: Cyber Security Disclaimer

    Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats.
  • Page 4: Table Of Contents

    Sensor Limits ....................... 33 Communication Connections ..................33 HMI and Tool Ports ..................... 34 Pin-Out Diagrams for HMI Connectors ..........35 10B/100B Ethernet Port ..................36 4 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 5 Point Database for Application 3916 ..............60 Point Database for Application 3924 ..............61 PXM10S/T Product Overview and Description ............. 62 Product Features ....................63 Communication Connections ............... 63 Requirements ...................... 63 5 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 6 Troubleshooting the LCD Panel Indications ............95 Resetting an I/O Module to Factory Settings ............97 Replacing a TX-I/O Plug-in Module ..............98 Replacing a TX-I/O Module Assembly ..............98 6 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 7: Compact Series Product Overview

    Otherwise, you cannot view features in newer firmware revisions, or the field panel may coldstart. 7 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 8: Bacnet Protocol Compatibility

    Device Registration Devices register with the DHCP server and Domain Name Server, if either is present. Address Assignment IP addresses are dynamically assigned by the DHCP server. 8 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 9: System Program

    The PXC Compact contains a non-volatile system program called , which can be upgraded in the field. The firmware is stored in Flash ROM memory, which keeps it 9 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 10: Minimum Firmware Revision Required

    See the APOGEE Field Panels Configuration and Sizing Guidelines (145-214) for more information on applications and functionality that can be activated through License Manager. See the License to enable SNMP Agent on Siemens Modular or Compact hardware with BACnet Firmware Revision 3.2.3 (LSM-SNMP) for information on adding licensed applications or functionality.
  • Page 11: Purpose Of Licenses

    EF.A or PXC24.2-EF.A which provides FLN and TX-I/O island bus support. Without replacing the PXC-16 or PXC-24 hardware or firmware, the customer can now install TX-I/O modules and expand the number of physical points. 11 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 12: Supported Point Types

    • Digital Binary/Digital Output Output Platinum 1K 375 or 385 alpha. Siemens, Johnson Controls, and DIN Standard Nickel. 10K and 100K Type 2 and 10K Type 3. Sensor supply 24 Vdc, 4.8W PXC-24 Supported Point Types. Configurable Points Dedicated Points...
  • Page 13 • Digital Binary/Digital Output Output Platinum 1K 375 or 385 alpha. Siemens, Johnson Controls, and DIN Standard Nickel. 10K and 100K Type 2 and 10K Type 3. Requires an external relay. Sensor supply 24 Vdc, 4.8W PXC-36 Supported Point Types.
  • Page 14: Pxc Compact Series, Rev 1 Hardware, Point Types

    (configurable) ● AO 1 – 3 Voltage Analog Output (AOV), dedicated ● Digital Output, DO 1 – 5 dedicated Landis & GYR Nickel 1000. Type 2. 14 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 15: 16- And 24-Point Compact Series Diagram

    25, 27, 28 Universal Input (+) (UI1 through UI3). – 26, 29 Signal Common. 30, 31, 33, 34, 36 Universal Input/Output (+) (U4 through U8). 15 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 16 OFF or ON solid - No device, no connection, or bad connection. PXC-16: DO 14 through DO 16; PXC-24: ON - Relay Energized. DO 20 through DO 24 16 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 17: 36-Point Compact Series Product Diagram

    64, 65, 67, 68, 70, 71, 73 – 40, 51, 54, 57, 60, 63, 66, 69, 72 Signal Common. 42, 44, 46, 48 24 Vdc external sensor power (+) source. 17 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 18 A RX or B RX OFF or ON solid - No device, no connection, or bad connection. DO 29 through DO 36 ON - Relay Energized. 18 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 19: Hardware Features

    The common for input and output analog points is floating and is not connected to the common of the 24 Vac input. Figure 1: Compact 16/24 Shared Ground Connections. 19 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 20: 24 Vdc External Sensor Power Source

    24 Vdc sensor power termination may be used as either a ground for the power or as a cable shield connection. "-" is not connected to earth ground. 20 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172...
  • Page 21: Custom Sensor Support

    The APOGEE firmware (program), its point database, PPCL program, trend data, and other information reside in the field panel memory. Memory consists of two areas: Flash Read-Only Memory (Flash ROM) and Random Access Memory (RAM). 21 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 22: Flash Read-Only Memory (Flash Rom)

    For procedures on using Auto-Restore and Database Backup to Flash, see the APOGEE P2 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual (125-3020). 22 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 23: Auto Save

    The PXC Compact Series contains one non-rechargeable AA (LR6) battery and one non-rechargeable coin cell (BR2032) battery that serve as a power backup in the event 23 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 24: Aa Battery

    Restore and Database Backup to Flash are not enabled, the information stored in RAM must be either reloaded from an Insight workstation, Datamate Base or Datamate Advanced, or entered again by an operator. 24 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 25: Aa Battery

    If Auto Restore and Database Backup to Flash have been enabled, the AA battery may be removed from the PXC Compact if there is not a requirement to maintain volatile data, such as Trend, over a power cycle. 25 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 26: Coin Cell Battery

    For more information on time synchronization, see the APOGEE P2 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual (125-3020) (125-3019 or 125-3020). 26 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 27: Coin Cell Battery

    The value of BATT2 is also set to 100 by a coldstart command. Since the controller is powered and the RTC oscillator does not stop, the value of BATT2 is valid and a time-date reset will not occur. 27 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 28: Memory Size And Typical Battery Backup Time

    (293 mm × 150 mm × 77 mm) DIN rail (EN 60715 TH 35-7.5, steel) 1.38" × 0.30" × 0.04" (35 mm × 7.5 mm × 1 mm) 28 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 29 1, no hardware flow control (Xon/Xoff supported). RJ-45 jack, 50 ft (16 m) max. cable length. Supports dial-in modem. Factory-set HMI Communication Speed PXC-16 and PXC-24: 9600 bps PXC-36: 115.2 Kbps 29 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 30 Digital Input (10 ms settling time) Short Circuit Current: 10 mA Supports counter inputs up to 20 Hz, minimum pulse duration 20 ms (open or closed) 30 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 31 Voltage (0-10 Vdc) Resolution: 2.2 mV Current (4-20 mA) Resolution: 4.4 µA 1K Ni RTD @ 32°F (Siemens, JCI, DIN Ni 1K) Resolution: 0.05 C 1K Pt RTD (375 or 385 alpha) @ 32°F Resolution: 0.08 C (375), 0.13 C (385) 10K NTC Type 2 or Type 3 Thermistor Resolution: 0.02 C to 0.10 C...
  • Page 32 Product meets OSHPD Special Seismic Preapproval certification (OSH-0217-10) under California Building Code 2010 (CBC2010) and International Building Code 2009 (IBC2009) when installed within the following Siemens enclosure part numbers: PXA-ENC18, PXA-ENC19, or PXA-ENC34. BACnet Testing Laboratories (BTL) Certified, Firmware Revision 3.0 and later 32 | 100 Siemens Industry, Inc.
  • Page 33: Sensor Limits

    HMI to reside on any of the following: ● BACnet/IP or Ethernet TCP/IP (P2) ALN ● RS-485 P2 or BACnet MS/TP ALN 33 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 34: Hmi And Tool Ports

    USB Device port does not support firmware flash upgrades. A driver must be loaded on the PC in order to communicate with the USB Device port. The driver is located in StdApps\Apogee\Firmware\USB Drivers. 34 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 35: Pin-Out Diagrams For Hmi Connectors

    Figure 3: RJ-11 Plug with Voids at Pins 1 and 8. Figure 4: P/N 540-143. Standard RJ-11 (6-pin) Tool Socket for RS-232 Devices. Description Description Not connected Not connected Ground 24 Vdc 35 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 36: 10B/100B Ethernet Port

    RS-485 port connects the PXC Compact to a P1 FLN where it emulates a TEC. ● When communicating on an RS-485 ALN, the Virtual AEM may be used to communicate with a P2 Ethernet network. 36 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 37: Fln Support

    An additional license is required to enable some of these FLN connections. Siemens Industry FLN The Siemens Industry Field Level Network (FLN) can consist of devices that communicate over an RS-485 connection using either MS/TP or Protocol 1 (P1). ●...
  • Page 38: Pxc Compact On P1

    The Alarm Printing and Report Printing settings have no effect on AEM operations (Virtual or hardware). – Baud rate settings have no effect on the data transmission. 38 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 39: Usb Host Port

    There are new menus available that allow for the identification of what HOA module is connected and communicating, along with the ability to view and customize the HOA switch mapping. 39 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 40: Hoa Specifications

    The default mapping is also used to allow the HOA board to command physical outputs before any logical points have been defined. 40 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 41: Communication

    After a warmstart, the field panel retains the HOA configuration. NOTE: The HOA must be connected to a field panel with Firmware Revision 2.8.5/3.2 or later in order to backup the HOA database. 41 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 42: Using The Hoa Switches

    Green I/O status LED will increase or decrease incrementally as the value changes. Manual Control Settings for Analog Outputs Switch Position % Output Voltage Mode Current Mode (LED Intensity) Output [V] Output [mA] 10.4 13.6 42 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 43 The logical point displays the opposite. For example, if the physical point is ON the Green I/O status LED will also be ON and the logical point will be OFF. 43 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 44: Pxc Compact On P1

    MMI Database Transfer. To keep the P2 point names unique in CT, the application number is added to the beginning of all corresponding point names. This application number is not used in the P1 database since subpoint names are always unique. 44 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 45: P1 Mode Application

    System Profile on the APPLICATIONS ALN (see the following figure). For example, Application 3015 is stored in PXC Compact node 15 on the APPLICATIONS30 ALN. 45 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 46: P1 Mode Operation

    ● PXC Compact on P1 displays as a TEC to ALN field panels and Insight software. It is compatible to all APOGEE revisions of firmware and software. 46 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 47: P1 Mode Enhanced Field Panel Point Team

    When the SYNC NOW point is commanded to YES, the SYNC HOUR value is copied to the HOUR point, and the MINUTE point is set to zero. 47 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 48: Tips For P1 Mode

    P1 Protocol message from its P1 host field panel in the last one minute. Note that this one-minute timeout value is configurable through the P1 TIMEOUT point, an AO point with a default value of one minute. 48 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 49: Miscellaneous

    After the UC database conversion is complete, add a fifth DO to the Application database. – Run the P2/P1 Application Converter tool to add the DO to the P1 point team. 49 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 50: Changing The Point Team Descriptor After Database Conversion

    Point Type in the P1 Point Team L2SL LDO* LENUM LPACI LAO ** * This article describes how to regain full L2SL functionality at the host field panel. 50 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 51: Identifying The Hardware Model Used In An Application Design

    2. In the Name field, add .PXC16 or .PXC24 to the existing name. Depending on your account settings, System Profile and MMI Database Transfer displays the hardware information in Name or System Name. 51 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 52: Making Changes To The Original Pxc Compact On P1 Database

    4. In System Profile, Tools, Auto Unbundling… window, delete the 3 application. 5. In System Profile, add the TECs back to the appropriate address locations. 52 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 53: Program To Allow Lpaci Points To Count Over The Lao Maximum Value

    LPACI point used to hold the full LPACI value. (Gain = 1.0) GAIN is a virtual LAO point used to hold the gain value of the LPACI point in the PXC Compact on P1. 53 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 54: Real Time Applications In A Pxc Compact On P1

    :BATT2. NOTE: If needed, access the AA battery status (RAM backup battery) from the host field [name] panel by using the unbundled point team :BATT. 54 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 55 00998C NORMAL TIME-DATE ROUTINES 01000… time-date routines -or-… stop execution and omit alternative non-time-date routines 00060IF(“3001.VTIME” .NE. ON) THEN GOTO 32000 . . . 32000GOTO 10 55 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 56 00120IF($VCRTM.GE.4.0.AND.$VCRTM.LT.5.0) THEN $VHOUR = 4.0 00130IF($VCRTM.GE.5.0.AND.$VCRTM.LT.6.0) THEN $VHOUR = 5.0 00140IF($VCRTM.GE.6.0.AND.$VCRTM.LT.7.0) THEN $VHOUR = 6.0 00150IF($VCRTM.GE.7.0.AND.$VCRTM.LT.8.0) THEN $VHOUR = 7.0 00160IF($VCRTM.GE.8.0.AND.$VCRTM.LT.9.0) THEN $VHOUR = 8.0 00170IF($VCRTM.GE.9.0.AND.$VCRTM.LT.10.0) THEN $VHOUR = 9.0 56 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 57 01998C ASSIGN YEAR TO GLOBAL VYEAR VALID VALUES 2000 TO 2058 02000IF($ARG6.EQ.ON) THEN GOTO 02070 02010$ARG1 = VYEAR 02018C ASSIGN MONTH TO FIELD PANEL MONTH VALID VALUES 1 TO 12 02020$ARG2 = $VMONTH 57 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 58: Synchronizing System Time In A Pxc Compact On P1

    01056C ENTER A GOSUB FOR EACH PXC COMPACT ON P1 WITH TIME HOSTED BY THIS FIELD PANEL 01058C SUBROUTINE SYNCHRONIZES TIME ONCE DAILY AT $VSYNHR 01060GOSUB 2100 "B2.AHU1:SYNC HOUR", "B2.AHU1:SYNC NOW" 58 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 59: Default Applications

    When the PXC-24 is using the default application, the 24 physical I/O points (1 to 24) in the PXC Compact on P1 are mapped to the corresponding P1 points 31 to 59 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 60: Point Database For Application 3916

    DEG F 0.05 -100.0 (DEG C) {39} 0.001 -5.0 {40} AO10 0.001 -5.0 {41} AO11 0.001 -5.0 {42} DI12 {43} DI13 {44} DO14 {45} DO15 {46} DO16 60 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 61: Point Database For Application 3924

    DEG F {41} 0.05 -100.0 (DEG C) {42} DEG F 0.05 -100.0 (DEG C) {43} {44} {45} {46} {47} AO17 0.001 -5.0 {48} AO18 0.001 -5.0 61 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 62: Pxm10S/T Product Overview And Description

    Product Description The PXM10S and PXM10T modules are available as an upgrade for use with all Siemens Compact and Modular Series field panels to provide additional local operator capabilities. The PXM10S and PXM10T modules are field mounted and replace the field panel covers.
  • Page 63: Product Features

    The PXM10S and PXM10T modules can be used with Compact platforms (PXC-36, PXC-24, and PXC-16), as well as with the PXC Modular field panels. NOTE: The PXM10S or PXM10T module firmware uses the proprietary Siemens PXM10 protocol to communicate with the host field panel. 63 | 100...
  • Page 64: Application Menus

    Hardware Platform The PXM10T and PXM10S modules can be used on all Siemens Compact and Modular series controllers. An additional connecting ribbon cable (part number PXA- HMI.CABLEP5) is required when mounting to a PXC16 or PXC24.
  • Page 65: Operator Display Layout

    BACstac revision number. Cursor position is indicated by either a right-angled bracket (>) or inverted text color, depending on field panel type and revision. Figure 6: Splash Screen 65 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 66 ● Alarm LED Off – if no off-normal or fault conditions are present, and no object is in the unacknowledged condition, the LED light is OFF. 66 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 67 Figure 7: INFO for Alarms Press ESC to close alarm window without affecting the alarm. 67 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 68: Operator Display Menu Tree

    HMI to unlock the user accounts by modifying that particular user account. Also, you can only change your password for the PXM10S or PXM10T modules from the HMI. 68 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies...
  • Page 69: Logging In

    E (Edit) (default setting) Alarm N (No_access) R (Read_only) C (Command) E (Edit) (default setting) Trend N (No_access) R (Read_only) C (Command) E (Edit) (default setting) 69 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 70 AutoLogoff delay. 1 to 1440 minutes. Disable automatic logoff. Password Expire Limit 0 to 365 days. Use for PXM10Tiny AutoLogin (Y/N) Enable automatic login. Disable automatic login. 70 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 71 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual (125-3020) (125-3019 or 125-3020). Do the following to automatically log in to the PXM10S or PXM10T module. Figure 8: Automatic Login Submenu 71 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 72 NOTE: If you make a mistake selecting a character, press character. Repeat until you ESC to return to the previous character. enter the complete user name. 72 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 73: Logging Off

    When you log off the module, the screen may go blank for approximately two seconds. Do the following to manually log off the PXM10S or PXM10T module. Figure 12: Logoff Menu 73 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 74: Navigation Menu

    ● INFO key activates additional information screen ● ALARM key activates unacknowledged alarm screen ● Main menu - alarms, display, monitor, settings, and logoff 74 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 75: Alarms Application Menu

    Alarm Ack screen for APOGEE from any point list screen ● Alarm Ack screen for BACnet from any point list screen ● Activate Alarm LED to mirror alarm bell icon - off, on solid 75 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 76 This option is only available for point(s) having alarms without acknowledging alarm. in an unacknowledged state. An affirmative response is interpreted as a confirmation to acknowledge all unacknowledged states. 76 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 77: Points (Command And Release) Application Menu

    Press DIAL/OK to apply change and return to truncated. previous screen. DIAL changes enumerated values. Press ESC to return to previous screen without changing priority. OK releases the selected priority. 77 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 78: Point Monitor Application Menu

    Title displays “Remove Monitor” submenu. Rotate DIAL to select Cancel. Confirms the selection. Press DIAL/OK to confirm or cancel the Once confirmed, all points in monitor are removed. selected operation. 78 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 79: Login Application Menu

    Rotate DIAL to select the desired login The title displays “Login” menu. method. Login options are: Automatic and Manual. Press DIAL/OK to accept the login method selected. 79 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 80: Settings Application Menu

    The Color feature is available only for the PXM10S module. ● Show Brightness screen with current value and accept update ● Show Timeout screen with current value and accept update 80 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 81: Unitary Equipment Controller

    However, it continues to support Confirmed Private Transfer (CPT) on all proprietary APOGEE messages, and is recognized as a Siemens device. ● The UEC can reference external objects using either Device Specific Name or BACnet Encoded Name.
  • Page 82 Save, upload and download database information using Field Panel Web Server UI (FPWeb UI)and Siemens Launch Pad. ● PPCL Assist for programming over the network using FPWeb UI and Siemens Launch Pad. ● Field panel support for FIN Builder graphics with Firmware Revision 3.3.1 and later.
  • Page 83: Unitary Equipment Controller Specifications

    USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps), Type A female connector. Configuration and Sizing Guidelines NOTE: See the documentation for supported speeds per controller model.. 83 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 84 Voltage (0-10 Vdc) Resolution: 2.2 mV Current (4-20 mA) Resolution: 4.4 µA 1K Ni RTD @ 32°F (Siemens, JCI, DIN Ni 1K) Resolution: 0.05 C 1K Pt RTD (375 or 385 alpha) @ 32°F Resolution: 0.08 C (375), 0.13 C (385) 10K NTC Type 2 or Type 3 Thermistor Resolution: 0.02 C to 0.10 C...
  • Page 85 EN 61000-4-2, 6 kV contact, 8 kV air discharge RF Conducted Immunity per EN 61000-4-6 @ 10V RF Radiated Immunity per EN 61000-4-3 @ 10V/m 85 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 86: Compact Series Smoke Control Application Requirements

    A USB-to-RS-232 adaptor may be needed for UL Listed modems or UL Listed printers that are not configured for USB communication. ● The modem may be located inside the PX Series enclosure. 86 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 87: Example Aln Configuration For Smoke Control Applications

    Namely, Ethernet requires UL listed switches and routers. The following figure displays a possible ALN configuration for smoke control. Figure 14: Example ALN Configuration for Smoke Control. 87 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 88: Service Information

    The battery is taped in the tray to secure it during shipping. The tape does not need to be replaced. 1. Pull the release tab on the curved side of the battery compartment cover. 2. Remove the battery compartment cover. 88 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 89: Reinstalling The Mounting Tabs

    3. Working from the center (inside) of the base, slide the mounting tab into the channel. (See the following figure.) NOTE: The end with the screw hole slides into the channel first. 89 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 90: Troubleshooting Compact Field Panels

    1. Verify that the device connected to the point is functioning properly and is not shorted out. 2. Verify that points are properly terminated on the termination board or module. 3. Verify that the correct voltage is supplied to the device. 90 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 91: Batt Low Led

    • If a 3.6 Volt lithium battery is used in standard PXC Compact models, the battery quickly discharges and provides much less backup protection than a 1.5 Volt alkaline battery. 91 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 92: Run Led

    S-pin (may also be marked as a reference pin [add image here]). 3. Verify the field panel address and communication speed. 4. Verify that the extended ALN trunk is operating. 92 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 93: Communication

    4. If needed, change the ALN type by entering the following at the HMI: S, H, F, C, E, M (System, Hardware, Fieldpanels, Config, nEttype, Modify). (S, H, F, C, S, T for Firmware Revision 2.8.3 and earlier.) 93 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 94: Errors

    2. Reset the module to factory settings. – Verify that the module is supplied with 24 Vdc. – Remove keys that are in the wrong module. 94 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 95: Troubleshooting The Lcd Panel Indications

    6. Troubleshoot using the LCD panel indications. 7. When done, remove the TXM1.8X-ML or TXM1.8U-ML plug-in module. 8. Reinsert the original plug-in module and its address key. 95 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 96 NTC resistance is too low (temperature over range). ● RTD resistance is too high (temperature over range). ● The voltage or current input is too high. 96 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25 Restricted...
  • Page 97: Resetting An I/O Module To Factory Settings

    6. Reinsert the address key.  After the reset, the modules operate with the factory default function for each I/O point. Any previous local override settings are deleted. 97 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 98: Replacing A Tx-I/O Plug-In Module

    When replacing a complete TX-I/O module assembly, the adjacent plug-in module on the male bus connector must first be removed from its terminal base. Otherwise, the module assembly catches on the bus connector. Figure 17: TX-I/O Module Removal. 98 | 100 Siemens Industry, Inc. Technical Reference Manual 145-172 Building Technologies 2018-09-25...
  • Page 99  As soon as the new module starts communicating with the PXC Modular, PXC-36, or P1 BIM, it is configured according to the module address and starts operation shortly afterward. 99 | 100 Technical Reference Manual 145-172 Siemens Industry, Inc. Building Technologies 2018-09-25 Restricted...
  • Page 100 Issued by © Siemens Industry, Inc., 2018 Siemens Industry, Inc. Technical specifications and availability subject to change without notice. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 +1 847-215-1000 Document ID: 145-172 Technical Reference Manual 145-172(MA) Edition: 2018-09-25...

Table of Contents